Desa BY35CEB Portable Forced Air Heaters, Service Procedures, Continued, Pump Pressure Adjustment

Models: BY100CEB BY35CEB BY70CEB BY150CEB

1 24
Download 24 pages 9 Kb
Page 10
Image 10
Air Output, Air Intake, and Lint Filters

R

PORTABLE FORCED AIR HEATERS

SERVICE

PROCEDURES

Continued

Air Output, Air Intake, and Lint Filters

1.Remove upper shell (see page 8).

2.Remove filter end cover screws using 5/16" nut-driver.

3.Remove filter end cover.

4.Replace air output and lint filters.

5.Wash or replace air intake filter (see Preventative Maintenance Schedule, page 6).

Air Intake Filter

Filter End

Fan Guard

Cover

Lint Filter

Air Output

Filter

Figure 16 - Air Output, Air Intake, and Lint Filters, 35/70,000 Btu/Hr Models

6.Replace filter end cover.

7.Replace fan guard and upper shell.

IMPORTANT: Do not oil filters

Pump Pressure Adjustment

1.Remove pressure gauge plug from filter end cover.

2.Install accessory pressure gauge (part number HA1180).

3.Start heater (see Operation, page 5). Allow motor to reach full speed.

4.Adjust pressure. Turn relief valve to right to increase pressure. Turn relief valve to left to decrease pressure. See specifications below for correct pres- sure for each model.

5.Remove pressure gauge. Replace pres- sure gauge plug in filter end cover.

Air Intake Filter

Filter End

Fan Guard

Cover

 

Lint Filter

Air Output

Filter

Figure 17 - Air Output, Air Intake, and Lint Filters, 100/150,000 Btu/Hr Models

Pressure

 

 

Gauge

 

Pump

Plug

 

Relief

 

Pressure

Model

(PSI/Bar)

Valve

35,000 Btu/Hr

2.9/0.200

 

70,000 Btu/Hr

5.2/0.359

 

100,000 Btu/Hr

3.9/0.269

 

150,000 Btu/Hr

4.8/0.331

Figure 18 - Pressure Gauge Plug Removal

(35/70,000 Btu/Hr Models Shown)

Pressure

Gauge

Figure 19 - Adjusting Pump Pressure

10

103618

Page 10
Image 10