TROUBLESHOOTING

TROUBLESHOOTING

TROUBLESHOOTING

OBSERVED PROBLEM WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.

15

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

Pilot will not stay lit

1.

Defective thermocouple

1.

Check pilot flame. It must impinge on

 

 

 

 

thermocouple

 

 

 

2.

Clean or adjust pilot for maximum flame

 

 

 

 

impingement on thermocouple

 

 

 

3.

Ensure the connection between valve

 

 

 

 

and thermocouple are tight and secure

 

 

 

4.

Check thermocouple with millivolt

 

 

 

 

meter. Take reading at thermocouple ter-

 

 

 

 

minals of gas valve with remote control

 

 

 

 

off. It should read 18 millivolts mini-

 

 

 

 

mum. Replace faulty thermocouple if

 

 

 

 

reading is below specified minimum

 

 

 

 

 

Pilot lit but no flame on burner

1.

Remote or wires defective

1.

Check remote wires for proper connec-

 

 

 

 

tions. Place jumper wire across termi-

 

 

 

 

nals at remote control. If burner comes

 

 

 

 

on, replace remote. If okay, place jumper

 

 

 

 

wire across remote control at valve. If

 

 

 

 

burner comes on, wires are faulty or con-

 

 

 

 

nections are bad

 

2.

Thermopile not generating sufficient

2.

Check thermopile with millivolt meter.

 

 

milivoltage

 

Take reading at thermopile terminals of

 

 

 

 

gas valve with remote control off. It

 

 

 

 

should read 325 millivolts minimum.

 

 

 

 

Replace thermopile if reading is below

 

 

 

 

specified minimum

 

3.

Plugged burner orifice

3.

Check burner orifice for stoppage and

 

 

 

 

remove

Frequent pilot outage

1. Pilot flame may be too low or blowing

 

(high) causing safety pilot to “drop out”

1.Clean and/or adjust pilot flame for maximum flame impingement on thermocouple

POSSIBLE CAUSEREMEDYManual backgroundManual backgroundManual backgroundForManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background.Manual backgroundManual backgroundManual backgroundManual background.comManual backgroundManual backgroundManual backgroundManual backgroundManual background