INSTALLATION
Connecting to Gas Supply (Cont.) Connecting Fireplace to Gas Supply
13
INSTALLATION
Continued
CAUTION: Use only new, black iron or steel pipe.
Gas Control | CSA |
| Equipment Shutoff Valve With |
| 1/8" NPT Tap* |
tain areas. Check your local codes. Use pipe of 1/2" or greater diameter to allow proper gas volume to fireplace. If pipe is too small, undue loss of volume will occur.
Installation must include a equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 21).
IMPORTANT: Install equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Check your building codes for special requirements for locating equipment shutoff valve to fireplaces.
Approved Flexible
Gas Hose
3" Minimum
Cap
Natural Gas
From Gas Meter (5" W.C.** to 10.5 W.C. Pressure)
Propane/LP
From External
Regulator (11"
W.C.** to 14"
W.C. Pressure)
Pipe Tee
Nipple Joint
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
We recommend that you install a sediment trap in supply line as shown in Figure 21. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into fireplace controls. If sediment trap is not installed or is installed wrong, fireplace may not run properly.
Sediment Trap
Figure 21 - Gas Connection
*Purchase the optional CSA
**Minimum inlet pressure for purpose of input adjustment.
CONNECTING FIREPLACE TO GAS SUPPLY
Installation Items Needed
•Phillips screwdriver
•sealant (resistant to propane/LP gas, not provided)
1.Route flexible gas line (provided by installer) from equip- ment shutoff valve into fireplace through side or rear access holes in outer casing (see Figure 22).
Propane/LP | External | |
Regulator | ||
Supply Tank | ||
|
Outer
Casing
Vent Pointing | Equipment |
Down | Shut Off |
| Valve |
Figure 20 - External Regulator with Vent Pointing Down
To Gas
Supply
Figure 22 - Routing Flexible Gas Line