AIR FOR COMBUSTION AND VENTILATION

Providing Adequate Ventilation (Cont.) Determining Fresh-Air Flow for Heater Location

5

AIR FOR COMBUSTION AND VENTILATION

Continued

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 6.

If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow for Heater Loca- tion, below.

Confined and Unconfined Space

National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

Gas water heater

 

30,000

Btu/Hr

Vent-free heater

+

26,000

Btu/Hr

Total

=

56,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 56,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/ Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Out- doors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

For morevisit www..com

111410-01C

Page 5
Image 5
Desa CF26NT installation manual Determining FRESH-AIR Flow for Heater Location, Confined and Unconfined Space

CF26NT specifications

Desa CF26NT is a modern gas fireplace that showcases a blend of contemporary design and efficient heating technology. Established to elevate the aesthetic appeal of homes while ensuring optimal warmth, the CF26NT stands out with its sleek lines and sophisticated finish. With a focus on user experience, this fireplace is not just a source of heat but a centerpiece that enhances any living space.

One of the main features of the Desa CF26NT is its innovative design, which allows it to fit seamlessly into various interior styles. The fireplace is built with a large viewing window, providing an expansive view of the flames. This not only adds to the ambiance but also creates a sense of openness in the room. The minimalist frame and clean edges contribute to a modern aesthetic, making it a perfect addition to contemporary living areas.

In terms of technology, the CF26NT utilizes advanced gas burning systems, which ensure efficient fuel use and lower emissions. This fireplace is designed to provide consistent heat output while minimizing the environmental impact. With adjustable flame heights, users can customize the intensity of the fire, allowing for a personalized heating experience that can cater to different occasions.

Moreover, the Desa CF26NT is equipped with a user-friendly control system that allows for effortless operation. The intuitive interface enables users to easily adjust the temperature and flame settings, ensuring comfort at their fingertips. For added convenience, many models come with remote control options, allowing users to operate the fireplace from the comfort of their seating area.

Another noteworthy characteristic of the CF26NT is its safety features. The fireplace includes an automatic shut-off system that activates in case of any malfunction or overheating, providing peace of mind for homeowners. Additionally, the unit is designed with insulated materials, ensuring that the exterior remains cool to the touch, making it safe for households with children and pets.

In conclusion, the Desa CF26NT is an exceptional choice for anyone looking to enhance their home with a stylish, efficient, and safe gas fireplace. Its combination of modern design, innovative technology, and user-centric features make it a standout option in the market for gas fireplaces today. Whether for heating or aesthetic purposes, the CF26NT promises to deliver an exceptional experience.