MANTEL CLEARANCES

OWNER’S MANUAL

INSTALLATION

Continued

MANTEL CLEARANCES

If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).

If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clear- ances shown in Figure 7 when using hood.

10"

8"

6"

2 1/2"

Minimum Non-

 

 

(A)

 

Combustible

Material

 

 

 

 

12"

 

 

 

 

Mantel Shelf

18"

 

20"

22"

 

 

 

 

 

Underside of

Mantel Shelf

All minimum distances are in inches

24" Floor Clearances Log Set

24"/30" Models

Top of Fireplace

Opening

NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the following:

operate the logs only with the flue damper open

raise the mantel to an accept- able height

remove the mantel

Minimum Non-

Distances to

Combustible

Underside of

Material Height

Mantel

Figure 6 - Minimum Mantel Clearances Without Using Hood

Mantel Shelf

Floor Clearances

A.If installing appliance on the floor level, you must maintain the minimum distance of 14" to combustibles (see Figure 8).

B.If combustible materials are less than 14" to the fireplace, you must install appliance at least 5" above the combus- tible flooring (see Figure 9).

 

12"

 

 

 

10"

 

 

 

8"

 

 

 

6"

 

 

 

2 1/2"

 

 

Minimum Non-

 

 

 

Combustible

 

 

 

Material

8"

12"

15"

 

 

Min.

 

 

 

Hood

Distances to

 

(GA6050, GA6052)

 

Underside of

 

 

 

 

Mantel

18"

Underside of

Mantel Shelf

All minimum distances are in inches

20"Manual background Log Set

All Models

Top of Fireplace Opening

Figure 7 - Minimum Mantel Clearances When Using Hood

 

Combustible

Hearth

14"

Material

 

Combustible

Min.

 

Material

 

 

5"

 

 

Min.

Non-Combustible Material

 

Figure 8 - Minimum Fireplace Clearances

Figure 9 - Minimum Fireplace Clearances

If Installed at Floor Level

 

Above Combustible Flooring

Continued

104306

9

Page 9
Image 9