OWNER’S MANUAL
INSTALLATION
Continued
MANTEL CLEARANCES
If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).
If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clear- ances shown in Figure 7 when using hood.
10"
8"
6"
2 1/2"
Minimum Non- |
|
| (A) |
| |||
Combustible | |||
Material |
| ||
|
|
| 12" |
|
|
|
|
Mantel Shelf
18" |
| 20" | 22" |
| |||
|
|
|
|
Underside of
Mantel Shelf
All minimum distances are in inches
24" Log Set
24"/30" Models
Top of Fireplace
Opening
NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the following:
•operate the logs only with the flue damper open
•raise the mantel to an accept- able height
•remove the mantel
Minimum Non- | Distances to |
Combustible | Underside of |
Material Height | Mantel |
Figure 6 - Minimum Mantel Clearances Without Using Hood
Mantel Shelf
Floor Clearances
A.If installing appliance on the floor level, you must maintain the minimum distance of 14" to combustibles (see Figure 8).
B.If combustible materials are less than 14" to the fireplace, you must install appliance at least 5" above the combus- tible flooring (see Figure 9).
| 12" |
|
|
| 10" |
|
|
| 8" |
|
|
| 6" |
|
|
| 2 1/2" |
|
|
Minimum Non- |
|
|
|
Combustible |
|
|
|
Material | 8" | 12" | 15" |
| |||
| Min. |
|
|
| Hood | Distances to | |
| (GA6050, GA6052) | ||
| Underside of | ||
|
| ||
|
| Mantel |
18"
Underside of
Mantel Shelf
All minimum distances are in inches
20" Log Set
All Models
Top of Fireplace Opening
Figure 7 - Minimum Mantel Clearances When Using Hood
| Combustible | Hearth |
14" | Material | |
| Combustible | |
Min. |
| Material |
|
| 5" |
|
| Min. |
| ||
Figure 8 - Minimum Fireplace Clearances | Figure 9 - Minimum Fireplace Clearances | |
If Installed at Floor Level |
| Above Combustible Flooring |
Continued
104306 | 9 |