Desa CGP20, RP30D Checking GAS Connections, Pressure Testing GAS Supply Piping System, Psig

Models: RP30D CGP20 CGP20L

1 24
Download 24 pages 14.62 Kb
Page 9
Image 9

OWNER’S MANUAL

CONNECTING TO GAS SUPPLY

Continued

IMPORTANT: Hold pressure regulator with wrench when connecting it to gas pip- ing and/or fittings.

*An A.G.A. design certified manual shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Pur- chase the optional A.G.A. design certified manual shutoff valve from your dealer. See Accessories, page 17.

CHECKING GAS CONNECTIONS

Pressure

Note: Burner bracket

Regulator

not shown for clarity

3/8" NPT

 

Pipe

 

Nipple

 

 

 

 

 

 

Heater

 

 

 

 

Ground Joint

Cabinet

 

 

Tee Joint

Union

 

 

 

Manual

 

Test

 

 

 

 

 

Reducer

Shutoff

 

Gauge

 

 

 

Bushing to 1/8"

Valve *

 

Connection *

 

NPT

 

Typical Inlet

 

 

 

 

 

 

 

 

 

1/8" NPT Plug

Pipe From

 

 

External Regulator

 

 

Tap

 

 

 

Tee Joint

(11" W.C. to 14"

 

 

 

 

 

 

W.C. Pressure)

 

Sediment

 

 

Pipe Nipple

3" Minimum

 

 

Trap

 

Cap

 

 

 

 

 

 

 

Figure 13 - Gas Connection

 

 

WARNING: Test all gas pip- ing and connections for leaks

after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

CAUTION: Make sure exter- nal regulator has been installed between propane/LP supply and heater. See guidelines under Con- necting to Gas Supply.

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test Pressures In Excess Of 1/2

PSIG

1.Disconnect heater and its individual manual shutoff valve from gas supply piping system. Pressures in excess of 1/2 PSIG will damage heater regulator.

2.Cap off open end of gas pipe where manual shutoff valve was connected.

3.Pressurize supply piping system by ei- ther using compressed air or

opening propane/LP supply tank valve.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Fig- ure 14).

Open

Manual

Shutoff

Valve

Closed

Figure 14 - Manual Shutoff Valve

2.Pressurize supply piping system by ei- ther using compressed air or opening propane/LP supply tank valve.

3.Check all joints from propane/LP sup- ply tank to manual shutoff valve (see Figure 15, page 10). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

PRESSURE TESTING

HEATER GAS

CONNECTIONS

1.Open manual shutoff valve (see Fig- ure 14).

2.Open propane/LP supply tank valve.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual shutoff valve to control valve (see Figure 15, page 10). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 10 and 11). Check the rest of the internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 11).

8. Replace front panel.

Continued

103569

9

Page 9
Image 9
Desa CGP20 Checking GAS Connections, Pressure Testing GAS Supply Piping System, Pressure Testing Heater GAS Connections