TROUBLESHOOTING

Continued

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

Burner does light after ODS/pilot is lit

1.

Burner orifice clogged

1.

Clean burner (see Cleaning and Mainte-

 

 

 

 

nance, page 19) or replace burner orifice

 

2.

Inlet gas pressure is too low

2.

Contact local natural gas company

 

3.

Burner orifice diameter is too small

3.

Replace burner orifice

 

 

 

 

 

Delayed ignition burner

1.

Manifold pressure is too low

1.

Contact local natural gas company

 

2.

Burner orifice clogged

2.

Clean burner (see Cleaning and Mainte-

 

 

 

 

nance, page 19) or replace burner orifice

 

 

 

 

 

Burner backfiring during combustion

1.

Burner orifice is clogged or damaged

1.

Clean burner (see Cleaning and Mainte-

 

 

 

 

nance, page 19) or replace burner orifice

 

2.

Damaged burner

2.

Replace damaged burner

 

3.

Gas regulator defective

3.

Replace gas regulator

 

 

 

 

 

Slight smoke or odor during initial operation

1.

Not enough air

1.

Check burner for dirt and debris. If

 

 

 

 

found, clean burner (see Cleaning and

 

 

 

 

Maintenance, page 19)

 

2.

Gas regulator defective

2.

Replace gas regulator

 

3.

Residues from manufacturing processes

3.

Problem will stop after a few hours of

 

 

and logs curing

 

operation

 

 

 

 

 

Moisture/condensation noticed on windows

1.

Not enough combustion/ventilation air

1.

Refer to Air for Combustion and Venti-

 

 

 

 

lation requirements (page 4)

 

 

 

 

 

Heater produces a whistling noise when

1.

Turning control knob to HI position

1.

Turn control knob to LO position and

burner is lit

 

when burner is cold

 

let warm up for a minute

 

2.

Air in gas line

2.

Operate burner until air is removed from

 

 

 

 

line. Have gas line checked by local

 

 

 

 

natural gas company

 

3.

Air passageways on heater blocked

3.

Observe minimum installation clear-

 

 

 

 

ances (see pages 7 through 9)

 

4.

Dirty or partially clogged burner orifice

4.

Clean burner (see Cleaning and Mainte-

 

 

 

 

nance, page 19) or replace burner orifice

White powder residue forming within burner box or on adjacent walls or furniture

1.When heated, vapors from furniture pol- ish, wax, carpet cleaners, etc. turn into white powder residue

1.Turn heater off when using furniture polish, wax, carpet cleaners, or similar products

www.desatech.com

Continued

104385

21

Page 21
Image 21
Desa CLD3018N, CLD3924NT, CCL3930NT(A) Troubleshooting, Continued, Maintenance, page, Refer to Air for Combustion and Venti

FAQ

How do I address delayed ignition?

Contact your local natural gas company if the manifold pressure is too low, or clean or replace the burner orifice.

What should I do about burner backfiring?

Clean or replace the burner orifice, or replace a damaged burner or gas regulator.

Why is there a whistling noise when the burner is lit?

Turn the control knob to the LO position and let it warm up, or operate the burner until air is removed from the line.