DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

________________________ Btu/Hr

 

 

 

 

Gas water heater*

 

________________________ Btu/Hr

Example:

 

 

 

Gas furnace

 

________________________ Btu/Hr

Gas water heater

 

40,000

Btu/Hr

Vented gas heater

 

________________________ Btu/Hr

Vent-free heater

+

31,500

Btu/Hr

 

71,500

Gas fireplace logs

 

________________________ Btu/Hr

Total

=

Btu/Hr

Other gas appliances* +

________________________ Btu/Hr

 

 

 

 

Total

=

________________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 71,500 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

Continued

104385

5

Page 5
Image 5
Desa CCL3930NT(A), CLD3018N Continued, Determining Fresh-Airflow For Heater Location, Air For Combustion And Ventilation

FAQ

What is the maximum Btu/Hr the space can support?

The maximum Btu/Hr the space can support is determined by dividing the space volume by 50 cubic feet.

How do I determine if I have a confined or unconfined space?

Use the provided worksheet to calculate the volume of the space and divide it by 50 cubic feet to determine if it is a confined or unconfined space.

What are the options for additional fresh air ventilation?

Options include adding the space of an adjoining room, venting the room directly to the outdoors, or installing a lower Btu/Hr heater to make the room unconfined.