Desa FB32C installation manual AIR for, Ventilation AIR

Models: FB32C

1 28
Download 28 pages 17.46 Kb
Page 9
Image 9

AIR FOR

VENTILATION AIR

 

COMBUSTION

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an

AND

adjoining unconfined space, you must provide two permanent openings: one within 12" of the

ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1

VENTILATION

and 2, Figure 4). You can also remove door into adjoining room (see option 3, Figure 4).

 

Continued

Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion

and Ventilation for required size of ventilation grills or ducts.

 

 

WARNING ICON

G 001 WARNING

 

Rework worksheet, adding the space of the adjoining unconfined

 

space. The combined spaces must have enough fresh air to supply all

 

appliances in both spaces.

 

 

 

 

12"

 

Ventilation

 

Ventilation Grills

 

Grills

 

 

Into Adjoining

Or

Into Adjoining Room,

 

Room,

Option 2

 

Remove

 

Option 1

 

 

Door into

 

 

 

 

 

 

Adjoining

 

 

 

Room,

 

 

 

Option

 

 

 

3

 

 

 

 

12"

Figure 4 - Ventilation Air from Inside Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

 

 

Outlet

 

 

 

Ventilated

 

 

 

 

 

Attic

 

 

Air

 

 

 

 

 

 

 

 

 

 

 

 

 

Outlet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To Attic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

¢QQQQ,,,,¢¢¢

To

 

 

 

 

Crawl

 

Inlet

 

 

Space

 

 

 

 

 

 

Inlet Air

Ventilated

 

 

 

Crawl Space

 

 

 

 

 

 

 

Figure 5 - Ventilation Air from Outdoors

9

103296

Page 9
Image 9
Desa FB32C installation manual AIR for, Ventilation AIR