AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow For Heater Location

AIR FOR COMBUSTION AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

 

 

 

Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

39,000

Btu/Hr

Total

=

79,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 79,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/ Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the ex- tra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventilation Air From Out- doors, page 7.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, thespaceisanunconfinedspace.Youwillneednoadditionalfreshairventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

For..com

108114

Page 6
Image 6
Desa INTERNATIONAL UNVENTED (VENT-FREE) GAS LOG HEATER installation manual Determining FRESH-AIR Flow for Heater Location

INTERNATIONAL UNVENTED (VENT-FREE) GAS LOG HEATER specifications

The Desa International Unvented (Vent-Free) Gas Log Heater stands as a remarkable solution for those seeking an efficient and aesthetically pleasing heating option for their homes. Recognized for its innovative design and advanced technology, this heater offers numerous benefits that cater to both functionality and style.

One of the main features of the Desa gas log heater is its vent-free design. This characteristic eliminates the need for ductwork or exhaust systems, allowing for easy installation in various locations, including living rooms, bedrooms, or recreational areas. With no external venting required, homeowners can enjoy increased flexibility in placement while saving on installation costs and labor. Moreover, the heater can fit seamlessly into existing fireplaces, creating a cozy ambiance without the need for traditional firewood.

Another standout feature of the Desa vent-free gas log heater is its exceptional energy efficiency. Utilizing infrared technology, the heater converts a high percentage of gas to heat, warming spaces quickly and reducing energy consumption. The unit is designed to operate with natural gas or propane, offering versatility depending on the homeowner's fuel preferences.

Safety is a top priority in the design of the Desa gas log heater. Equipped with an automatic shut-off system and an oxygen depletion sensor, the heater ensures secure operation by shutting down in case oxygen levels drop too low. This added safety feature provides peace of mind for families, allowing for safe use even during extended periods of operation.

Aesthetically, the Desa International gas log heater does not compromise on style. With an array of realistic log designs and finishes, homeowners can choose a heater that complements their interior decor perfectly. The unit’s flame effects mimic traditional wood-burning fires, enhancing the warm ambiance of any room.

In conclusion, the Desa International Unvented (Vent-Free) Gas Log Heater offers a unique combination of efficiency, safety, and aesthetics. Its vent-free design allows for flexible installation, while infrared heating technology ensures quick warmth and energy savings. Coupled with enhanced safety features and an attractive appearance, this gas log heater provides a practical and stylish heating solution for any home.