VENTING INSTALLATION INSTRUCTIONS

Installation for Vertical Termination (Cont.) High Altitude Installation Parts Lists for Venting Kits and Components

15

VENTING INSTALLATION INSTRUCTIONS

Continued

Vertical Venting

V = 40' max.

Note: Install restrictor into inner collar of fireplace as shown.

45° Elbow

Figure 24 - Vertical Venting Configuration With No Horizontal Run (Vertical Round High Wind Termination Shown)

HIGH ALTITUDE INSTALLATION

Your DESA direct-vent fireplace has been tested and approved for elevations from 0-2000 feet (USA) and elevations from 0-4500 feet (Canada).

When installing this fireplace at an elevation above 2000 feet (in the USA), you may need to decrease the input rating by changing the existing burner orifice to a smaller size. Reduce input 4% for each 1000 feet above sea level. Check with your local gas company for proper orifice size identification.

When installing this fireplace at an elevation above 4500 feet (in Canada), check with local authorities.

Consult your local gas company to help determine the proper orifice for your location.

For assistance with any high altitude installation contact DESA’s Customer Service Department at 1-866-672-6040.

PARTSLISTSFORVENTINGKITSANDCOMPONENTS DESA (5/8") Pipe & Vent Kits

Number

Description

P58-6

6" Section Double Wall Pipe, Galvanized

P58-12

12" Section Double Wall Pipe, Galvanized

P58-24

24" Section Double Wall Pipe, Galvanized

P58-36

36" Section Double Wall Pipe, Galvanized

P58-48

48" Section Double Wall Pipe, Galvanized

PA58-712

Adjustable 7"-12" Section Double Wall Pipe, Galvanized

FPA58-6

6" Duravent Collar to FMI Pipe Adaptor (6" Collar/Pipe

 

Section)

DPA58-6

6" FMI Collar to Pipe Duravent Adaptor (6" Collar/Pipe

 

Section)

E58-45

45° Elbow, Galvanized

E58-90

90° Elbow, Galvanized

FSE58-45

45° Starter Elbow, Galvanized (Duravent Collar to

 

FMI Pipe)

DSE58-45

45° Starter Elbow, Galvanized (FMI Collar to Duravent

 

Pipe)

VKG-58

Ground Floor Vent Kit

VKB-58

Basement Vent Kit

VKS-58

Snorkel Vent Kit

VKR-58

Roof Vent Kit

VKC-58

Corner Vent Kit

HTK

Horizontal Round Termination Kit

HT-58

Horizontal Round Termination, Galvanized

HTKS-58

Horizontal Square Termination Kit

HTS-58

Horizontal Square Termination, Galvanized

VT-58

Vertical Round Termination, Galvanized

ST-58-14

14" Snorkel Termination, Galvanized

ST-58-36

36" Snorkel Termination, Galvanized

SC-58

Storm Collar, Galvanized

WF-58

Wall Firestop, Galvanized

RF-58-6

Roof Flashing - 0 to 6/12 Pitch, Galvanized

RF-58-12

Roof Flashing - 6/12 to 12/12 Pitch, Galvanized

VR-58

Vertical Restrictor, Galvanized

S-58

Vinyl Siding Standoff, Galvanized

WS-58

Wall Strap

CS-58

Cathedral Ceiling Support

FP-58

Firestop Plate

SF-58

Stucco Flashing - For use with HTS-5

For morevisit www..com

111922-01C

Page 15
Image 15
Desa K42EN, K42EP installation manual High Altitude Installation, Number Description