LFP33PR
UNVENTED PROPANE/LP GAS FIREPLACE
INSTALLATION
Continued
Mantel Clearances for Built-In Installation
If placing mantel above
If your installation does not meet the above minimum clearances, you must:
• raise the mantel to an acceptable height
OR
• remove the mantel
INSTALLING GAS PIPING TO FIREPLACE LOCATION
WARNING: A qualified ser- vice person must connect fire- place to gas supply. Follow all local codes.
CAUTION: Never connect heater directly to the propane/LP supply. This heater requires an ex- ternal regulator (not supplied). In- stall the external regulator between the heater and propane/LP supply.
Installation Items Needed
Before installing fireplace, make sure you have the items listed below.
•external regulator (supplied by installer)
•piping (check local codes)
•sealant (resistant to propane/LP gas)
•manual shutoff valve *
•test gauge connection *
•sediment trap
•tee joint
•pipe wrench
•approved flexible gas line with gas connec- tor (if allowed by local codes) (not provided)
* An A.G.A. |
valve with 1/8" NPT tap is an acceptable |
alternative to test gauge connection. Pur- |
Wall board or facing material (above firebox) may be of combustible material, including decorative mantel ornaments or other similar projec- tions off of the facing material.
Framing
Material
Firebox
Mantel Shelf
10"
8"
6"
2 1/2"
Noncombustible Material May Project Off this Surface above the Firebox Hood
13" 16" 19" 21"
chase the optional A.G.A. |
manual shutoff valve from your dealer. See |
Accessories, pages 24 and 25. |
The installer must supply an external regu- lator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incom- ing gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure
16.Pointing the vent down protects it from freezing rain or sleet.
CAUTION: Use only new, black iron or steel pipe. Inter-
Supplied Firebox
Hood Must Be
Used at All Times
Note: All vertical measurements are from top of fireplace hood opening to bottom of mantel shelf.
These minimum clearances replace any other recommended clearances supplied with your ANS Z21.11.2 approved gas logs.
your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to fireplace. If pipe is too small, undue loss of pressure will occur.
Propane/LP
Supply
External Tank
Regulator
Figure 15 - Minimum Mantel Clearances for
Vent
Pointing
Down
Figure 16 - External Regulator with Vent
Pointing Down
10 | 104888 |