Desa Checking Gas Connections, LFP33PR UNVENTED PROPANE/LP GAS FIREPLACE, Installation

Models: LFP33PR

1 30
Download 30 pages 51.56 Kb
Page 12
Image 12
CHECKING GAS

LFP33PR

UNVENTED PROPANE/LP GAS FIREPLACE

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

Pressure Testing Gas Supply Piping System WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

Pressure Testing Fireplace Gas Connections WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG

1. Disconnect fireplace and its individual

manual shutoff valve from gas supply

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Fig- ure 20).

2.Pressurize supply piping system by ei- ther using compressed air or opening propane/LP supply tank valve.

3.Check all joints from propane/LP sup- ply to manual shutoff valve (see Fig- ure 21). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

4.Correct all leaks at once.

Open

Manual

Shutoff

Valve

Closed

Figure 20 - Manual Shutoff Valve

Pressure Testing Fireplace Gas Connections

1.Open manual shutoff valve (see Fig- ure 20).

2.Open propane/LP supply tank valve.

3.Make sure control knob of fireplace is in the OFF position.

4.Check all joints from manual shutoff valve to thermostat gas valve (see Fig- ure 21). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Light fireplace (see Operating Fire- place, pages 16 and 17). Check all other internal joints for leaks.

7.Turn off fireplace (see To Turn Off Gas to Appliance, page 17).

 

piping system. Pressures in excess of 1/2

 

psig will damage fireplace gas regulator.

2.

Cap off open end of gas pipe where

 

manual shutoff valve was connected.

3.

Pressurize supply piping system by ei-

 

ther using compressed air or opening

 

propane/LP supply tank valve.

4.

Check all joints of gas supply piping

 

system. Apply mixture of liquid soap

 

and water to gas joints. Bubbles form-

 

ing show a leak.

5.

Correct all leaks at once.

6.

Reconnect fireplace and manual shutoff

 

valve to gas supply. Check reconnected

 

fittings for leaks.

Manual Shutoff Valve

Propane/LP

Supply Tank

Manual Gas Valve

Figure 21 - Checking Gas Joints