PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

INSTALLATION

Continued

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.

4.Check all joints of gas supply piping system. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fit- tings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.

Close equipment shutoff valve (see Figure 15).

2.

Pressurize supply piping system by either

5.Correct all leaks at once.

6.Light heater (see Operating Heater, page 14). Check all other internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appli- ance, page 15).

8.

Replace front panel.

 

Equipment

Open

Shutoff Valve

 

 

 

Closed

 

Figure 15 - Equipment Shutoff Valve

 

Gas

 

 

Meter

 

 

 

Equipment

 

 

Shutoff Valve

Figure 16 - Checking Gas Joints for

Natural Gas

 

opening propane/LP supply tank valve for

 

propane/LP gas or opening main gas valve

 

located on or near gas meter for natural gas

 

or using compressed air.

3.

Check all joints from gas meter for natural gas

 

(see Figure 16) or propane/LP supply tank for

 

propane/LP gas, to equipment shutoff valve

 

(see Figure 17). Apply a noncorrosive leak

 

detection fluid to all joints. Bubbles forming

 

show a leak.

4.

Correct all leaks at once.

PRESSURE TESTING HEATER GAS

Propane/LP Supply Tank

Equipment

Shutoff Valve

CONNECTIONS

1.Open equipment shutoff valve (see Figure 15).

2.For natural gas open main gas valve located on or near gas meter. For propane/LP gas open propane/LP supply tank valve.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from equipment shutoff valve to thermostat gas valve (see Figure 16 or 17). Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

Figure 17 - Checking Gas Joints for
Propane/LP Gas

116292-01A

www.desatech.com

13

Page 13
Image 13
Desa LSL18NT Installation, Continued, Pressure Testing Gas Supply Piping System, Checking Gas Joints for Natural Gas