20

FIREPLACE INSTALLATION

Connecting Fireplace To Gas Supply Checking Gas Connections

FIREPLACE INSTALLATION

Continued

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

5/16" hex socket wrench or nut-driver

sealant (resistant to propane/LP gas, not provided)

1.Open lower louver door panel by gently pulling forward.

2.Route flexible gas line (provided by installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace.

3.Attach flexible gas line from gas supply to control valve (see Figure 32).

4.Check all gas connections for leaks. See Checking Gas Connections.

To Gas Supply

 

 

(Natural)

Equipment

 

To External

Control

Shutoff Valve

Regulator

Valve

 

(Propane/LP)

 

 

Flexible Gas Line

Do NOT Kink

Figure 32 - Attaching Flexible Gas Line to Control Valve

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

4.Check all joints of gas supply piping system. Apply noncorro- sive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5.Reconnect fireplace and equipment shutoff valve to gas sup- ply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 33).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air.

3.Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 34 for propane/LP or Figure 35 for natural gas). Apply noncorrosive leak detec- tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Equipment

Shutoff Open

Valve

Closed

Figure 33 - Equipment Shutoff Valve

Propane/LP

Equipment

Shutoff

Supply Tank

Valve

 

 

Gas Valve

Figure 34 - Checking Gas Joints for Propane/LP Gas Fireplace

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect fireplace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/ LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace, or using compressed air.

Equipment

Shutoff

Valve

Gas

Meter

Gas Valve

Figure 35 - Checking Gas Joints for Natural Gas Fireplace

For..com

108661

Page 20
Image 20
Desa T32N, T36N, T32P, T36P Connecting Fireplace to GAS Supply, Checking GAS Connections, Installation Items Needed

T32N, T36N, T32P, T36P specifications

Desa T32N, T36N, T32P, and T36P are prominent technologies that represent the cutting-edge advancements in the field of telecommunications and data transmission. These systems are crucial for a variety of applications, including telecommunications networks, data centers, and various other technological infrastructures that require high-speed and reliable data transfer capabilities.

Starting with the T32N and T36N models, these systems are characterized by their exceptional bandwidth capacity and high processing speeds. They are designed to cater to the growing demand for faster internet connections and efficient data handling. One of the main features of these models is their ability to support multiple channels simultaneously, allowing for numerous data streams to be processed at once. This is particularly beneficial for environments where data traffic is high, such as urban areas and corporate networks. The T32N and T36N utilize advanced modulation techniques to enhance signal quality, effectively minimizing interference and increasing overall throughput.

On the other hand, the T32P and T36P models are specially engineered for optimal performance under varying network conditions. These models are equipped with adaptive technologies that automatically adjust to network demands, ensuring consistent data delivery even during peak usage periods. The main trait of these systems is their resilience; they are built to withstand fluctuations in data traffic and environmental factors, making them suitable for deployment in diverse settings, from rural areas to densely populated cities.

All four models leverage state-of-the-art technologies such as MIMO (Multiple Input Multiple Output) and beamforming to maximize efficiency and coverage. MIMO technology allows these systems to transmit and receive multiple data streams simultaneously, significantly boosting the data rate and overall system capacity. Beamforming enhances the directivity of the signal, focusing the transmission toward specific receivers, which not only improves signal strength but also reduces interference with other devices.

Another noteworthy characteristic of the Desa T32N, T36N, T32P, and T36P family is their compatibility with a wide range of existing technologies and infrastructures. This interoperability allows for seamless integration into current systems, facilitating upgrades without the need for complete overhauls. As the landscape of technology continues to evolve, these models stand out for their robust features and adaptive capabilities, solidifying their position as essential tools in the advancement of telecommunications and data transfer solutions.