VENTING INSTALLATION INSTRUCTIONS

Installation Planning (Cont.)

 

 

VENTING INSTALLATION INSTRUCTIONS

Continued

Minimum Pipe

Overlap 11/4"

Direct Vent

Pipe

Wall

Firestop

Maintain 1"

Minimum Air

Space Around

Outer Pipe When

Penetrating a Wall

10" x 10" Framed Opening

Siding Standoff

Screws

High Wind

Termination

Apply Mastic to

Outside Edge of

Standoff

Exterior Wall with Vinyl Siding

WARNING: Never run vent downward as this may cause excessive temperatures which could cause a fire. Operation of improperly installed and main- tained venting system could result in serious injury, property damage or loss of life.

GROUND FLOOR INSTALLATION

Recommended Applications:

Installation using cabinet surrounds

Through the wall using round or square termination (up to 12" horizontal pipe)

NOT FOR CORNER INSTALLATION

Adjustable

45° Elbow

Pipe 12" Max.

 

Horizontal High

Wind Square

Termination

Wall Firestop

Square Termination

Vertical (V)

Horizontal (H)

29" min.

17" max.

Figure 13 - Typical Horizontal Termination Cap Mounting with Additional Siding Standoff Installed

Horizontal Termination Configurations

Figures 14 through 18 show different configurations and alternatives for venting with horizontal termination. Each figure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: Remember that a horizontal run of venting must have a 1/4" rise for every 12" of run toward the termination.

45° Elbow

 

Exterior Portion of Wall

 

 

 

 

 

 

 

Wall

 

Firestop (Round

Firestop

 

Termination Only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Round

Slide Ring

Termination

Cap

Over Elbow to

 

Complete

 

Connection

 

Round Termination

(Kit HTK Shown)

 

Figure 14 - Horizontal Termination Configuration for Square and Round Terminations

For..com

111986-01A

Page 10
Image 10
Desa T32P, T32N installation manual Horizontal Termination Configurations, Square Termination, 17 max