Desa T32N, T32P installation manual Venting Installation Instructions, Continued

Models: T32N

1 38
Download 38 pages 48.12 Kb
Page 11
Image 11
Recommended Applications:

VENTING INSTALLATION INSTRUCTIONS

Installation Planning (Cont.)

11

VENTING INSTALLATION INSTRUCTIONS

Continued

CORNER AND ALTERNATE INSTALLATION

Recommended Applications:

Corner ground floor installation

Ground floor installation where pipe vents horizontally through wall (over 12" horizontal pipe)

Basement installation where one foot clearance from ground to termination is possible

 

Not to Exceed

90° Elbow

 

(H) Limits

Wall

 

 

 

Firestop

 

As Required for (V)

 

 

 

 

See Chart for Pipe

 

 

Section Required

Square

 

 

Termination

45°

 

 

 

 

Elbow

 

 

Required

 

 

 

 

 

 

 

 

 

 

 

Vertical (V)

Vertical Pipe

Horizontal (H)

*401/2" min.

None

30" max.

511/2" min.

1 ft.

48" max.

631/2" min.

2 ft.

60" max.

751/2" min.

3 ft.

84" max.

871/2" min.

4 ft.

20' max.

*Note: Ground Floor Corner Venting

 

Not to Exceed

 

(H) Limits

 

 

 

 

 

 

 

 

 

 

Square

 

 

 

 

 

 

 

 

 

 

 

 

 

90° Elbow

 

 

 

 

 

 

 

 

 

 

Termination

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wall

 

Firestop

12" Minimum

45° Elbow

Figure 15 - Horizontal Termination Configuration for Corner Installation Using One 90° Elbow

SNORKEL TERMINATION INSTALLATION

Recommended Applications:

Installations requiring a vertical rise on building exterior

Any installation using snorkel termination to achieve one foot above ground

Snorkel terminations are available for installations requiring a vertical rise on the exterior of the building. If installing snorkel termination below grade, you must provide proper drainage to prevent water from entering snorkel termination (see Figure 16). Do not back fill around snorkel termination.

Snorkel

Snorkel

 

Wall

Termination

 

Termination

 

Firestop

90° Elbow

 

 

 

12"

45°

 

 

Minimum

 

 

Elbow

 

 

 

 

12"

 

 

 

Minimum

 

 

 

 

Adequate

 

 

 

Drainage

 

 

Snorkel

Termination

12"

Minimum

Figure 16 - Snorkel Termination Configurations for Below Ground Installation

Manual backgroundFor moreManual backgroundManual backgroundManual backgroundvisit www.Manual backgroundManual backgroundManual background.comManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

111986-01A

Page 11
Image 11
Desa T32N, T32P Venting Installation Instructions, Continued, Recommended Applications Corner ground floor installation