SPLIT OAK AND AMERICAN OAK DESIGN 18", 24" AND 30" MODELS

AIR FOR COMBUSTION AND VENTILATION

Continued

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

________ Btu/Hr (maximum the

space can support)

________ Btu/Hr (actual amount of

Btu/Hr used)

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

VENTILATION AIR WARNING: Rework worksheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

Example: 51,200 Btu/Hr (maximum the space can support)

73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a con-

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills Into Adjoining Room,

fined space because the actual Btu/Hr used

Room,

Or

Option 2

Option 1

Remove

is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventila- tion grills between rooms. See Ventila- tion Air From Inside Building.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

Ventilation Air From Inside BuildingWARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space, provide ad- equate combustion and ventila- tion air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3.

Door into Adjoining Room, Option Ventilation Air From Outdoors 3

12"

Figure 3 - Ventilation Air from Inside Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

Crawl Space

 

 

Figure 4 - Ventilation Air from Outdoors

103427

5

Page 5
Image 5
Desa Unvented Propane Gas Log Heater Model Split Oak and American Oak Design installation manual Continued, Ventilation Air