UNVENTED PROPANE GAS LOG HEATER
INSTALLATION
NOTICE: A qualified service per- son must install heater. Follow all local codes.
IMPORTANT:
bustion and Ventilation, pages 4 and 5.
42"
NOTICE: State or local codes may only allow operation of this appli- ance in a vented configuration. Check your state or local codes.
WARNING: Before installing
CHECK GAS TYPE |
| |
Use only propane gas. If your gas supply is |
| |
not propane, do not install heater. Call |
| |
dealer where you bought heater for proper | 16" | |
type heater. | ||
|
in a solid fuel burning fireplace, the chimney flue and firebox must be cleaned of soot, creosote, ashes and loose paint by a quali- fied chimney cleaner. Creosote will ignite if highly heated. In- spect chimney flue for damage. If damaged, operate heater with flue damper closed.
WARNING: Seal any fresh air vents or ash
WARNING: Never install the heater
•in a bedroom or bathroom un- less installed as a vented ap- pliance, see page 8
•in a recreational vehicle
•where curtains, furniture, clothing, or other flammable objects are less than 36 inches from the front, top, or sides of the heater
•in high traffic areas
•in windy or drafty areas
CAUTION: This heater cre- ates warm air currents. These currents move heat to wall sur- faces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities in the air (such as tobacco smoke) exist, may discolor walls.
INSTALLATION AND
CLEARANCES
(Vent-Free Operation Only)
WARNING: Maintain the mini- mum clearances. If you can, pro- vide greater clearances from floor, ceiling, and adjoining wall.
MINIMUM FIREPLACE CLEARANCE TO COMBUSTIBLE MATERIALS
Log Size | 18", 24", 30" |
|
|
Side Wall | 16" |
|
|
Ceiling | 42" |
|
|
Floor | 5" |
|
|
LOG SIZING REQUIREMENTS
Log |
| Minimum Firebox Size | ||
Size | Height | Depth | Front Width | |
18" |
| 17" | 14" | 20" |
24" |
| 17" | 14" | 26" |
30" |
| 17" | 14" | 32" |
|
|
|
|
|
Carefully follow the instructions below. This will ensure safe installation into a masonry or U.L. listed manufactured fireplace.
Minimum Wall and Ceiling Clearances (see Figure 5)
A.Clearances from the side of the fire- place opening to any combustible wall should not be less than 16 inches.
B.Clearances from the top of the fireplace opening to the ceiling should not be less than 42 inches.
Figure 5 - Minimum Clearance to Wall and Ceiling
NOTICE: Manual control heaters may be used as a vented product. If so, you must always run heater with chimney flue damper open. If running heater with damper open,
Minimum Non Combustible Material Clearances
If Not Using Mantel
Note: If using a mantel, go to page 7. If not using a mantel, follow the information on this page.
You must have non combustible material(s) above the fireplace opening. Non combus- tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have non combustible material behind it. Non combustible mate- rial must extend at least 8" up (for all mod- els). If non combustible material is less than 12", you must install the fireplace hood accessory (24" and 30" models only). See chart on page 7, column 1 and Figure 5 for minimum clearances.
IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 8.
Continued
6 | 103427 |