Desa UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER Continued, Vanguard Flame-Max

Models: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER

1 24
Download 24 pages 28.18 Kb
Page 4
Image 4
Continued

VANGUARD FLAME-MAX™

UNVENTED PROPANE/LP GAS LOG HEATER

AIR FOR COMBUSTION AND VENTILATION

Continued

Unusually Tight Construction

The air that leaks around doors and win- dows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is de- fined as construction where:

a.walls and ceilings exposed to the outside atmosphere have a con- tinuous water vapor retarder with a rating of one perm (6x10-11kg per pa-sec-m2) or less with open- ings gasketed or sealed and

b.weather stripping has been added on openable windows and doors and

c.caulking or sealants are applied to areas such as joints around window and door frames, be- tween sole plates and floors, be- tween wall-ceiling joints, be- tween wall panels, at penetra- tions for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide ad- ditional fresh air. See Ventilation Air From Outdoors, page 5.

If your home does not meet all of the three criteria above, proceed to De- termining Air Flow For Heater Loca- tion.

Confined and Unconfined Space

The National Fuel Gas Code (ANSIZ223.1, 1992 Section 5.3) defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are in-

stalled*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventila- tion grills between them.

DETERMINING AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height =

__________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_______________ (volume of space)

÷50 cu. ft. = (maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can sup- port)

3.Add the Btu/Hr of all fuel burning ap- pliances in the space.

Vent-free heater __________ Btu/Hr Gas water heater* ________ Btu/Hr Gas furnace _____________ Btu/Hr

Vented gas heater _________ Btu/Hr

Gas fireplace logs ________ Btu/Hr

Other gas appliances* + ___ Btu/Hr

Total

= ___ Btu/Hr

Example:

 

 

Gas water heater

40,000

Btu/Hr

Vent-free heater

+ 31,500

Btu/Hr

Total

= 71,500 Btu/Hr

*Do not include direct-vent gas appli- ances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________ Btu/Hr (maximum the

space can support)

__________ Btu/Hr (actual amount of

Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

71,500 Btu/Hr (actual amount of Btu/ Hr used)

The space in the above example is a con- fined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventila- tion grills between rooms. See Ventila- tion Air From Inside Building, page 5.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 5.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

4

104256

Page 4
Image 4
Desa UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER installation manual Continued, Determining Air Flow For Heater Location