Desa UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER installation manual Installation, Continued

Models: UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER

1 24
Download 24 pages 28.18 Kb
Page 7
Image 7
Minimum Non Combustible Material Clearances

OWNER’S MANUAL

INSTALLATION

Continued

NOTICE: Manual control heaters may be used as a vented product. If so, you must always run heater with chimney flue damper open. If running heater with damper open, non-combustible material above fireplace opening is not needed. Go to Installing Damper Clamp Accessory for Vented Op- eration, page 9.

Minimum Non Combustible Material Clearances

If Not Using Mantel

Note: If using a mantel, go to column 3. If not using a mantel, follow the information on this page.

You must have non combustible material(s) above the fireplace opening. Non combus- tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have non combustible material behind it. Non combustible mate- rial must extend at least 8" up (for all mod- els). If non combustible material is less than 12", you must install the fireplace hood accessory (24", 30", and 36” models only). See chart below and Figure 4 on page 6 for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 9.

If Using Mantel

You must have non combustible material(s) above the fireplace opening. Non combus- tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have non combustible material behind it. Non combustible mate- rial must extend at least 8 inches up (for all models). If non combustible material is less than 12", you must install the fireplace hood accessory (24", 30”, and 36" models only). Even if non combustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See chart below and Figures 6 and 7, page 8, for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 9.

Non-Combustible

Requirements for

Material Distance (A)

Safe Installation

 

 

12" or more

Non combustible material OK.

Between 8" and 12"

24", 30", or 36” Models: Install fireplace hood accessory

 

(GA6050 or GA6052, see Accessories, page 19).

 

18" Model: Non combustible material OK.

Less than 8"

Non combustible material must be extended to at least 8".

 

See Between 8" and 12", above. If you cannot extend

 

material,you must operate heater with flue damper open.

 

 

Heat Resistant Heat Resistant

Material

(A)

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace

Continued

104256

7

Page 7
Image 7
Desa UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER Installation, Continued, Minimum Non Combustible Material Clearances