Venting Installation

instructions

Continued

Vertical Termination Configurations

Figures 21 through 24 show four different configurations for verti- cal termination.

Venting with Two 90° Elbows

Vertical (V)

Horizontal (H1) +

 

Horizontal (H2)

5' min.

2' max.

6' min.

4' max.

7' min.

6' max.

8' min.

8' max.

20' max.

8' max.

45° Elbow

Note: Install restrictor into inner collar of fireplace as shown.

Figure 21 - Vertical Venting Configuration Using Two 90° Elbows with Two Horizontal Runs (Vertical Round High Wind Termination Shown)

Venting with One 90° Elbow

 

Vertical (V)

Horizontal (H)

 

5' min.

2' max.

 

6' min.

4' max.

 

7' min.

6' max.

 

8' min.

8' max.

45° Elbow

20' max.

8' max.

 

 

Note: Install restrictor into inner collar of fireplace as shown.

Figure 22 - Vertical Venting Configuration Using One 90° Elbow (Vertical Round High Wind Termination Shown)

Venting with Two 90° Elbows

Vertical (V1)

Horizontal (H)

5' min.

6' max.

6' min.

12' max.

7' min.

18' max.

8' min.

20' max.

Note: Install restrictor into inner collar of

fireplace as shown.

45° Elbow

Note: Vertical (V1) + Vertical (V2) = 40' max.

Figure 23 - Vertical Venting Configuration Using Two 90° Elbows (Vertical Round High Wind Termination Shown)

Vertical Venting

V = 40' max.

Note: Install restrictor into inner collar of fireplace as shown.

45° Elbow

Figure 24 - Vertical Venting Configuration With No Horizontal

Run (Vertical Round High Wind Termination Shown)

111906-01F

www.desatech.com

13

Page 13
Image 13
Desa V42V-A installation manual Vertical Termination Configurations, Venting with One 90 Elbow, Vertical Venting