CHECKING GAS

FIREPLACE MANUFACTURERS INC.

UNVENTED NATURAL GAS LOG HEATER

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

Pressure Testing gas Supply Piping system WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

Pressure Testing Heater Gas ConnectionsWARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing gas Supply Piping system

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Fig- ure 14).

2.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to equipment shutoff valve (see Figure 15). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Open

Equipment

ShutoffClosed

Valve

Pressure Testing Heater Gas Connections

1.Open equipment shutoff valve (see Fig- ure 14).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from equipment shutoff valve to gas control (see Figure 15). Apply mixture of liquid soap and wa- ter to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 14 through 16). Check all other internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 15).

1.Disconnect appliance with its appliance main gas valve (control valve) and equip- ment shutoff valve from gas supply pip- ing system. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was con- nected.

3.Pressurize supply piping system by either using compressed air or open- ing main gas valve located on or near gas meter.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check re- connected fittings for leaks.

Figure 14 - Equipment Shutoff Valve

Equipment Shutoff Valve

Gas Control

Location

 

Gas Meter

Figure 15 - Checking Gas Joints