Venting Installation

instructions

Continued

Minimum Pipe

Siding Standoff

Overlap 11/4"

 

Direct-Vent

 

Pipe

Screws

Wall

 

Firestop

 

Maintain 1"

 

Minimum Air

High Wind

Space Around

Termination

Outer Pipe When

Apply

Penetrating a Wall

Mastic to

 

 

Outside

10" x 10" Framed

Edge of

Standoff

Opening

 

Exterior Wall with Vinyl Siding

Figure 13 - Typical Horizontal Termination Cap Mounting with Additional Siding Standoff Installed

Horizontal Termination Configurations Figures 14 through 18 show different configura- tions and alternatives for venting with horizontal termination. Each figure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: If using a venting configuration of only horizontal venting with no vertical run, a 1/4" rise for every 12" of run toward the termination is required.

NOTICE: Do not seal termination cap to vent pipe. Cap must be removable for vent inspection and maintenance.

WARNING: Never run vent downward as this may cause excessive temperatures which could cause a fire. Operation of improperly installed and main- tained venting system could result in serious injury, property damage or loss of life.

GROUND FLOOR INSTALLATION

Recommended Applications:

Installation using cabinet surrounds

Through the wall using round or square termina- tion (up to 12" horizontal pipe)

NOT FOR CORNER INSTALLATION

Adjustable

Horizontal Pipe 12" Max. 45° Elbow

High Wind

Square

Termination

Wall Firestop

Square Termination

Vertical (V)

 

 

 

Horizontal (H)

29" min.

 

 

 

17" Max.

 

 

 

 

 

Exterior Portion

45° Elbow

 

of Wall Firestop

Wall

 

(Round

 

Termination

Firestop

 

Only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slide Ring

Over Elbow to Complete Connection

Round Termination Cap

Round Termination

(Kit HTK Shown)

*If installing this fireplace at altitudes of

4000 feet and above, it is recommended that an additional vertical height of 6" be added to the vent system.

Figure 14 - Horizontal Termination Configuration for Square and Round Terminations

111987-01D

www.desatech.com

11

Page 11
Image 11