CONNECTING FIREPLACE TO GAS SUPPLY

Fireplace

Installation

Continued

Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 32).

IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location. The main gas valve is for turning on or shutting off the gas to the appliance.

Check your building codes for any special re- quirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.

Figure 33 - Connecting Flexible Gas Line WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install a sediment trap/ drip leg in supply line as shown in Figure 32. Lo- cate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and fireplace. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sedi- ment trap traps moisture and contaminants. This keeps them from going into fireplace gas controls. If sediment trap/drip leg is not installed or is in- stalled wrong, fireplace may not run properly.

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

• 5/16" hex socket wrench or nut-driver

• sealant (resistant to propane/LP gas, not provided)

1.Open lower louver door panel by gently pull- ing forward.

2.Route flexible gas line (provided by installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace.

3.Attach flexible gas line from gas supply to control valve (see Figure 33).

4.Check all gas connections for leaks. See

Checking Gas Connections.

Flexible Gas Line

Red Surface

Indicates For

Do NOT Kink

Propane/LP

Equipment

 

Use Only

Shutoff Valve

 

 

1/2" NPT

Inlet

 

Incoming

Pressure

Outlet

Gas Line

Tap

Pressure Tap

Note: Wire Connections Not Shown for Clarity

Figure 33 - Connecting Flexible Gas Line

to Electronic Valve

CHECKING GAS CONNECTIONS

Approved Flexible Gas Line

CSA Design-Certified Equipment Shutoff Valve with 1/8" NPT

Tap*

3" Minimum

 

Natural - From Gas Meter (5.5" W.C. to 10.5" W.C. Pressure)

Propane/LP

From External

Regulator (11" W.C. to 14" W.C. CHECKING GAS CONNECTIONS Pressure)

Figure 32 - Gas ConnectionWARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

Manual background WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detec-

Cap Pipe Nipple Tee Joint

Sediment Trap/Drip Leg

Figure 32 - Gas Connection

*The CSA design-certified equipment shutoff valve may be supplied with the appliance or you can purchase it from your retailer.

tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

111987-01D

www.desatech.com

21

Page 21
Image 21
Desa (V)T32EN SERIES, (V)T32EP SERIES installation manual Connecting Fireplace To Gas Supply, Checking Gas Connections