DMP Electronics XR20A, XR6A, XR10A manual Installation, Standby Current

Models: XR10A XR6A XR20A

1 18
Download 18 pages 62.18 Kb
Page 12
Image 12
Standby Current

Installation

XR6A/XR10A/XR20A STANDBY BATTERY POWER CALCULATIONS

 

Standby Current

Alarm Current

 

 

 

 

 

Command Processor Panel

 

50mA ______ mA

 

50mA ______ mA

Active Zones 1-9

Qty _____ x

1.6mA ______ mA

Qty _____ x

*2mA ______ mA

Active Zone 10 (zone 6 on XR6A)

 

4mA ______ mA

 

30mA ______ mA

2-Wire Smoke Detectors

Qty _____ x

.1mA ______ mA

Qty _____ x

.1mA ______ mA

Bell Output

 

 

1500mA max. ______ mA

670, 770, and 771 Keypads

Qty _____ x

125mA ______ mA

Qty _____ x 125mA ______ mA

Annunciator (ON)

 

 

Qty _____ x

20mA ______ mA

690, 790, 791, and 793 Keypads

Qty _____ x

100mA ______ mA

Qty _____ x 100mA ______ mA

Annunciator (ON)

 

 

Qty _____ x

20mA ______ mA

692 Keypads

Qty _____ x

30mA ______ mA

Qty _____ x

30mA ______ mA

Annunciator (ON)

 

 

Qty _____ x

10mA ______ mA

710 Bus Splitter/Repeater

Qty _____ x

30mA ______ mA

Qty _____ x

30mA ______ mA

711 or 714 Zone Expander

Qty _____ x

7mA ______ mA

Qty _____ x

7mA ______ mA

Active Zones (EOL installed)

Qty _____ x

1.6mA ______ mA

Qty _____ x

*2mA ______ mA

715 Zone Expander

Qty _____ x

7mA ______ mA

Qty _____ x

7mA ______ mA

Active Zones (EOL installed)

Qty _____ x

4mA ______ mA

Qty _____ x

30mA ______ mA

2-Wire Smokes

Qty _____ x

.1mA ______ mA

Qty _____ x

.1mA ______ mA

714-8 or 714-16 Point Zone Expanders

 

20mA ______ mA

 

20mA ______ mA

Active Zones (EOL installed)

Qty _____ x

1.6mA ______ mA

Qty _____ x

*2mA ______ mA

715-8 or 715-16 Point Zone Expanders

 

20mA ______ mA

 

20mA ______ mA

Active Zones (EOL installed)

Qty _____ x

4mA ______ mA

Qty _____ x

30mA ______ mA

2-Wire Smokes

Qty _____ x

.1mA ______ mA

Qty _____ x

.1mA ______ mA

733 Wiegand Interface

 

30mA ______ mA

 

30mA ______ mA

Active Zones (EOL installed)

Qty _____ x

1.6mA ______ mA

Qty _____ x

*2mA ______ mA

Annunciator (ON)

 

 

 

20mA ______ mA

738A Ademco Wireless Interface

 

75mA ______ mA

 

75mA ______ mA

w/Receiver

 

 

 

 

FA426 16 Point Receiver

 

50mA ______ mA

 

50mA ______ mA

740/741/743 SC Keypads

Qty _____ x

50mA ______ mA

Qty _____ x 100mA ______ mA

Annunciator (ON)

 

 

Qty _____ x

20mA ______ mA

Auxiliary Powered Devices on

 

 

 

 

Terminals 7 and 11

 

______ mA

 

______ mA

(Other than keypads)

 

 

 

 

Total Standby ___________ mA

Total Alarm ____________ mA

Total Standby ____________ mA x number of standby hours needed ______ = ___________ mA/hours

*Based on 10% of active zones in alarm condition

Total Alarm + ___________ mA/hours

Total ___________ mA/hours

x _.001_____

= ___________ A/hours required

XR6A/XR10A/XR20A Installation Guide

Digital Monitoring Products

2841 E. Industrial Drive Springfield, MO USA 65802-6310 800-641-4282

Page 8

Page 12
Image 12
DMP Electronics XR20A, XR6A, XR10A manual Installation, Standby Current