Installation
Bell Output
7.1Terminals 5 and 6
Nominal 12 VDC is supplied by terminal 5 on the panel to power alarm bells or horns. The output is rated for a maximum of 1.5 Amps with a 40VA transformer and 600mA with a 20VA transformer. This output can be steady or pulsed depending upon the Bell Action specified in Output Options programming. Terminal 6 is the ground reference for the bell circuit.
Keypad Data Bus
8.1Description
Terminals 7, 8, 9, and 10 of the XR6A/XR10A/XR20A panel are designated as the keypad data bus. In addition to keypads, the XR20A allows the connection of any combination of zone expanders to the data bus up to a maximum of four devices. The XR6A allows the connection of four zones on address one.
8.2Terminal 7 - RED
Nominal 12 VDC is supplied at terminal 7 to power Security Command keypads and zone expanders. This is also where power for any auxiliary device is supplied. The ground reference for terminal 7 is terminal 10. The maximum output is rated at 500mA. All auxiliary devices totaled together must not exceed the panel's maximum current rating of 500mA.
8.3Terminal 8 - YELLOW
Data receive from keypads and zone expanders.
8.4Terminal 9 - GREEN
Data transmit to keypads and zone expanders.
8.5Terminal 10 - BLACK
Terminal 10 is the ground reference for Security Command keypads, zone expanders, and any auxiliary devices being powered by terminals 7 and 11.
Smoke and Glassbreak Detector Output
9.1Terminal 11
Nominal 12 VDC at 100mA maximum (shared by terminal 25) is supplied at terminal 11 to power
XR6A/XR10A/XR20A Installation Guide
2841 E. Industrial Drive Springfield, MO USA | Digital Monitoring Products |
Page 9