Installation
Powered Zone for 2-Wire Smoke Detectors
11.1Terminals 25 and 26
A resettable
For programming purposes, the zone number is 10 on the XR10A/XR20A and zone 6 on the XR6A. The zone uses a Model 309, 3.3k W EOL resistor (provided with the panel) and has an operating range of 8.8 to 14.2 VDC.
Power is dropped from zone 10 any time a Sensor Reset is performed on the panel. Whenever
The UL compatibility identifier is: A.
Manufacturer | Model | Detector | Base | Base ID | # of | XR | Zone Expander | |
ID | Detectors | Panel | ||||||
|
|
|
|
| ||||
|
|
|
|
|
|
|
| |
Detection Systems | DS282 | B | None | N/A | 10 | 10/20 | 715, | |
|
|
|
|
|
|
|
| |
Detection Systems | DS282TH | B | None | N/A | 10 | 10/20 | 715, | |
|
|
|
|
|
|
|
| |
Detection Systems | DS250 | B | MB2W | A | 10 | 10/20 | 715, | |
|
|
|
|
|
|
|
| |
Detection Systems | DS250TH | B | MB2W/MB2WL | A | 10 | 10/20 | 715, | |
|
|
|
|
|
|
|
| |
Detection Systems | DS250HD | B | MB2W/MB2WL | A | 10 | 10/20 | 715, | |
|
|
|
|
|
|
|
| |
Hochiki | 20 | 10/20 | 715, | |||||
|
|
|
|
|
|
|
| |
DMP/Hochiki | 7 | 10/20 | 715, | |||||
|
|
|
|
|
|
|
| |
DMP/Hochiki | 7 | 10/20 | 715, | |||||
|
|
|
|
|
|
|
| |
Sentrol/ESL | 429AT | S09A | None | N/A | 12 | 10/20 | 715, | |
|
|
|
|
|
|
|
| |
Sentrol/ESL | 521B | S09A | None | N/A | 12 | 10/20 | 715, | |
|
|
|
|
|
|
|
| |
Sentrol/ESL | 521BXT | S09A | None | N/A | 12 | 10/20 | 715, | |
|
|
|
|
|
|
|
| |
System Sensor | 1100 | STD | None | N/A | 10 | 20 | 715 | |
|
|
|
|
|
|
|
| |
System Sensor | 1151 | STD | B110LP | N/A | 10 | 20 | 715 | |
|
|
|
|
|
|
|
| |
System Sensor | 1400 | STD | None | N/A | 10 | 10/20 | 715 | |
|
|
|
|
|
|
|
| |
System Sensor | 1451 | STD | B401, B401B | N/A | 10 | 10/20 | 715 | |
|
|
|
|
|
|
|
| |
System Sensor | 2100 | STD | None | N/A | 10 | 10/20 | 715 | |
|
|
|
|
|
|
|
| |
System Sensor | 2400 | STD | None | N/A | 10 | 10/20 | 715 | |
|
|
|
|
|
|
|
| |
System Sensor | 2451 | STD | B401, B401B, DH400 | N/A | 10 | 10/20 | 715 | |
|
|
|
|
|
|
|
| |
System Sensor | 1451DH | STD | DH400 | N/A | 10 | 10/20 | 715 | |
|
|
|
|
|
|
|
| |
System Sensor | 2100T | STD | None | N/A | 10 | 10/20 | 715 | |
|
|
|
|
|
|
|
| |
System Sensor | 2400AT | STD | None | N/A | 10 | 10/20 | 715 | |
|
|
|
|
|
|
|
| |
System Sensor | 2400AIT | STD | None | N/A | 10 | 10/20 | 715 | |
|
|
|
|
|
|
|
| |
System Sensor | 2400TH | STD | None | N/A | 10 | 10/20 | 715 | |
|
|
|
|
|
|
|
| |
System Sensor | 2451TH | STD | B401, B401B | N/A | 10 | 10/20 | 715 | |
|
|
|
|
|
|
|
|
Figure 4: Compatible 2-wire smoke detectors
XR6A/XR10A/XR20A Installation Guide
2841 E. Industrial Drive Springfield, MO USA | Digital Monitoring Products |
Page 11