DreamGEAR N185, P186, P314 Leak Checking, Pressure Testing-Gassupply Piping System, Before Testing

Models: N313 N185 P186 P314

1 23
Download 23 pages 21.4 Kb
Page 11
Image 11
LEAK CHECKING:

Pressure

Regulator

3/8" NPT Pipe Nipple

 

 

 

Tee Joint

 

 

 

Test

 

Reducer

Gauge

 

 

Bushing to

 

 

Connection

 

1/8" NPT

 

 

 

1/8" NPT

 

 

 

Plug Tab

Sediment

 

 

Tee Joint

 

 

Pipe

Trap

 

 

Nipple

 

 

 

 

 

 

Cap

 

 

 

Heater Cabinet

Ground Joint Union

Manual

 

 

Shutoff

 

 

Valve

 

Natural Gas

 

 

From

 

(7" W.C. to

 

10.5" W.C. Pressure)

Gas Meter

 

 

 

 

 

L.P Gases

 

 

(11.0" W.C. to

 

 

14.0" W.C. Pressure)

 

 

Figure 8

LEAK CHECKING:

GENERAL : Although all gas connections on the heater are leak tested at the factory prior to shipment, a complete gas tightness check must be performed at the installation site due to possible mishandling in shipment, or excessive pressure unknowingly being applied to the appliance. Periodically check the whole system for leaks, or immediately check if the smell of gas is detected.

BEFORE TESTING

Do not smoke while leak testing. Extinguish all open flames.

Make a soap solution of one part liquid detergent and one part water. You will need a spray bottle, brush or a piece of rag to apply the solution to the fittings.

For LP units, check with a full cylinder.

CAUTION : NEVER LEAK TEST WITH AN OPEN FLAME

PRESSURE TESTING-GAS SUPPLY PIPING SYSTEM

The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig.

The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to less than 1/2psig.

Page 10

Page 11
Image 11
DreamGEAR N185, P186, P314, N313 installation manual Leak Checking, Pressure Testing-Gassupply Piping System, Before Testing