Menu 2: System Status (continued)

Item and Sample

 

Password to

 

Range

Explanation

Display

 

Change

 

 

 

 

 

 

 

 

 

2 6

 

No change

 

0-0XFFFF

This is a hexadecimal alarm status value used by CheckUPS

Show Alarm Code #2

 

allowed.

 

 

software.

almcode2 0000 hex

 

 

 

 

 

 

 

 

 

 

 

2 7

 

No change

 

List

This parameter shows why the UPS transferred from AC input

Transfer Code

 

allowed.

 

 

power to battery power. (Possible causes are system/battery test,

xfercode

 

 

 

 

brownout, line loss, manual, frequency, or reset.)

 

 

 

 

 

 

2 8

 

User

 

List

This parameter provides control of the system test.

Test Control

 

 

 

 

 

testcon

 

 

 

 

 

 

 

 

 

 

 

2 9

 

No change

 

List

This parameter shows the results of the last system test.

Test Results

 

allowed.

 

 

 

tresults

 

 

 

 

 

2 10

 

None

 

Not

 

 

 

By pressing ¿ while displaying this parameter, you can start a User

Test Alarm

 

 

 

applicable.

Test alarm to make sure the FERRUPS alarms properly or to test

testalarm

 

 

 

 

alarm contacts at the DB9 communication port. By pressing ¿ again,

 

 

 

 

 

you can stop the User Test alarm.

 

 

 

 

 

 

Menu 3: System Status Info

Item and Sample

Password to

Range

Explanation

 

Display

Change

 

 

 

 

 

 

 

3

1

User

0001-2459

Time (displayed in 24-hour time). The FERRUPS uses this time to

Unit Time

 

 

record alarms and battery power operation in its logs. (See Section

time 01:15

 

 

506.)

 

 

 

 

 

3

2

User

0101-1231

Date. The FERRUPS uses this date to record alarms and battery

Unit Date

 

 

power operation in its logs. (See Section 506.)

date = 07/08

 

 

 

 

 

 

 

 

3

3

User

1994-2130

Year.

Unit Year

 

 

 

year 1998

 

 

 

 

 

 

 

 

3

4

No change

65-300

The input voltage the FERRUPS is receiving. When this value drops

AC Input Volts

allowed.

 

below the brownout voltage, the FERRUPS switches to battery

acvin 120 V

 

 

power.

 

 

 

 

 

3

5

No change

65-300

The voltage the FERRUPS is providing to your equipment.

AC Output Volts

allowed.

 

 

acvout 120 V

 

 

 

 

 

 

 

 

3

6

No change

1.0-900.0

The current the FERRUPS is drawing from the AC input source.

AC Input Current

allowed.

 

 

aciin 16.7 A

 

 

 

 

 

 

 

 

3

7

No change

1.0-900.0

The current your equipment is drawing from the FERRUPS.

AC Output Current

allowed.

 

 

aciout 16.7

 

 

 

 

 

 

 

 

3

8

No change

Not

Volt-amperes out. The total apparent power your equipment is

VA Out

allowed.

applicable.

drawing from the FERRUPS. This value is based on parameter 3 4

vaout 2 KVA

 

 

multiplied by parameter 3 6.

 

 

 

 

 

3

9

No change

Not

Watts out. The total real power your equipment is drawing from the

Watts Out

allowed.

applicable.

FERRUPS.

watts 1.4 kW

 

 

 

 

 

 

 

 

14