Item and Sample |
| Password to |
| Range | Explanation |
Display |
| Change |
|
|
|
|
|
|
|
|
|
2 6 |
| No change |
| This is a hexadecimal alarm status value used by CheckUPS | |
Show Alarm Code #2 |
| allowed. |
|
| software. |
almcode2 0000 hex |
|
|
|
|
|
|
|
|
|
|
|
2 7 |
| No change |
| List | This parameter shows why the UPS transferred from AC input |
Transfer Code |
| allowed. |
|
| power to battery power. (Possible causes are system/battery test, |
xfercode |
|
|
|
| brownout, line loss, manual, frequency, or reset.) |
|
|
|
|
|
|
2 8 |
| User |
| List | This parameter provides control of the system test. |
Test Control |
|
|
|
|
|
testcon |
|
|
|
|
|
|
|
|
|
|
|
2 9 |
| No change |
| List | This parameter shows the results of the last system test. |
Test Results |
| allowed. |
|
|
|
tresults |
|
|
|
|
|
2 10 |
| None |
| Not |
|
|
| By pressing ¿ while displaying this parameter, you can start a User | |||
Test Alarm |
|
|
| applicable. | Test alarm to make sure the FERRUPS alarms properly or to test |
testalarm |
|
|
|
| alarm contacts at the DB9 communication port. By pressing ¿ again, |
|
|
|
|
| you can stop the User Test alarm. |
|
|
|
|
|
|
Item and Sample | Password to | Range | Explanation | |
| Display | Change |
|
|
|
|
|
|
|
3 | 1 | User | Time (displayed in | |
Unit Time |
|
| record alarms and battery power operation in its logs. (See Section | |
time 01:15 |
|
| ||
|
|
|
|
|
3 | 2 | User | Date. The FERRUPS uses this date to record alarms and battery | |
Unit Date |
|
| power operation in its logs. (See Section 506.) | |
date = 07/08 |
|
|
| |
|
|
|
|
|
3 | 3 | User | Year. | |
Unit Year |
|
|
| |
year 1998 |
|
|
| |
|
|
|
|
|
3 | 4 | No change | The input voltage the FERRUPS is receiving. When this value drops | |
AC Input Volts | allowed. |
| below the brownout voltage, the FERRUPS switches to battery | |
acvin 120 V |
|
| power. | |
|
|
|
|
|
3 | 5 | No change | The voltage the FERRUPS is providing to your equipment. | |
AC Output Volts | allowed. |
|
| |
acvout 120 V |
|
|
| |
|
|
|
|
|
3 | 6 | No change | The current the FERRUPS is drawing from the AC input source. | |
AC Input Current | allowed. |
|
| |
aciin 16.7 A |
|
|
| |
|
|
|
|
|
3 | 7 | No change | The current your equipment is drawing from the FERRUPS. | |
AC Output Current | allowed. |
|
| |
aciout 16.7 |
|
|
| |
|
|
|
|
|
3 | 8 | No change | Not | |
VA Out | allowed. | applicable. | drawing from the FERRUPS. This value is based on parameter 3 4 | |
vaout 2 KVA |
|
| multiplied by parameter 3 6. | |
|
|
|
|
|
3 | 9 | No change | Not | Watts out. The total real power your equipment is drawing from the |
Watts Out | allowed. | applicable. | FERRUPS. | |
watts 1.4 kW |
|
|
| |
|
|
|
|
|