900 Specifications
Model | ||||||||||
| 2 kVA/1.4 kW | 3 kVA/2.1 kW | 4.5 kVA/3.2 kW | 6 kVA/4.2 kW | 7.5 kVA/5.3 kW | |||||
|
|
|
|
|
|
|
| |||
AC Input Voltage | 110 = 22 amps | 110 = 30 amps | 110 = 40 amps | 208 | = 28 amps | 208 | = 36 amps | |||
and Current | 115 = 22 amps | 115 = 30 amps | 115 = 40 amps | 220 | = 28 amps | 220 | = 36 amps | |||
| 120 | = 22 amps | 120 | = 30 amps | 120 | = 40 amps | 230 | = 28 amps | 230 | = 36 amps |
| 127 | = 22 amps | 127 | = 30 amps | 127 | = 40 amps | 240 | = 28 amps | 240 | = 36 amps |
| 208 | = 12 amps | 208 | = 16 amps | 208 | = 20 amps |
|
|
|
|
| 220 | = 12 amps | 220 | = 16 amps | 220 | = 20 amps |
|
|
|
|
| 230 | = 12 amps | 230 | = 16 amps | 230 | = 20 amps |
|
|
|
|
| 240 | = 12 amps | 240 | = 16 amps | 240 | = 20 amps |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Recommended Input | 120 | = | 120 | = | 120 | = | 208 | = | 208 | = |
Service for 60 Hz U.S. | 208 | = | 208 | = | 208 | = | 240 | = | 240 | = |
Models* | 240 | = | 240 | = | 240 | = |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Output Voltage and | 120 | = 16 amps | 120 | = 25 amps | 120 | = 37 amps | 120 | = 50 amps | 120 | = 62 amps |
Maximum Output | 127 | = 15 amps | 127 | = 23 amps | 127 | = 35 amps | 127 | = 47 amps | 127 | = 59 amps |
Current in Amps** | 208 | = 9 amps | 208 | = 14 amps | 208 | = 21 amps | 208 | = 28 amps | 208 | = 36 amps |
| 220 | = 9 amps | 220 | = 13 amps | 220 | = 20 amps | 220 | = 27 amps | 220 | = 34 amps |
| 230 | = 8 amps | 230 | = 13 amps | 230 | =19 amps | 230 | = 26 amps | 230 | = 32 amps |
| 240 | = 8 amps | 240 | = 12 amps | 240 | = 18 amps | 240 | = 25 amps | 240 | = 31 amps |
|
|
|
|
|
| |||||
Efficiency on AC Line | 90% | 90% | 90% | 89% | 89% | |||||
|
|
|
|
|
|
| ||||
On Line BTU/hour: | 703 |
| 1024 | 1427 | 1707 | 2116 | ||||
kW/hour: | 0.206 | 0.300 | 0.418 | 0.500 | 0.620 | |||||
|
|
|
|
|
| |||||
Audible Noise (dB) | <45 dB | <45 dB | <45 dB | <45 dB | <45 dB | |||||
|
|
|
|
|
|
|
|
|
|
|
Typical Standard |
|
|
|
|
|
|
|
|
|
|
Runtime (minutes) |
|
|
|
|
|
|
|
|
|
|
Full Load: | 11 minutes | 17 minutes | 10 minutes | 16 minutes | 12 minutes | |||||
Half Load: | 23 minutes | 36 minutes | 22 minutes | 38 minutes | 27 minutes | |||||
|
|
|
|
|
|
|
|
|
|
|
Weights: |
|
|
|
|
|
|
|
|
|
|
No Internal Bypass, |
|
|
|
|
|
|
|
|
|
|
Standard Batteries: | 280 lbs. (127 kg) | 327 lbs. (148.3 kg) | 383 lbs. (173.7 kg) | 563 lbs. (255.4 kg) | 635 lbs. (288 kg) | |||||
Internal Bypass, |
|
|
|
|
|
|
|
|
|
|
Standard Batteries: | 303 lbs. (137.4 kg) | 350 lbs. (158.8 kg) | 410 lbs. (186 kg) | 590 lbs. (267.6 kg) | 662 lbs. (300.3 kg) | |||||
Battery Cabinet, |
|
|
|
|
|
|
|
|
|
|
Standard Batteries: |
|
|
|
|
|
|
|
|
|
|
FBT21 | 235 lbs. (106.6 kg) | 235 lbs. (106.6 kg) | 235 lbs. (106.6 kg) | 235 lbs. (106.6 kg) | 235 lbs. (106.6 kg) | |||||
FBT22 | 355 lbs. (161 kg) | 355 lbs. (161 kg) | 355 lbs. (161 kg) | 355 lbs. (161 kg) | 355 lbs. (161 kg) | |||||
FBT31 | 418 lbs. (189.6 kg) | 418 lbs. (189.6 kg) | 418 lbs. (189.6 kg) | 418 lbs. (189.6 kg) | 418 lbs. (189.6 kg) | |||||
FBT32 | 660 lbs. (299.4 kg) | 660 lbs. (299.4 kg) | 660 lbs. (299.4 kg) | 660 lbs. (299.4 kg) | 660 lbs. (299.4 kg) | |||||
|
|
|
|
|
|
|
| |||
UPS Dimensions |
| 27.25 x 13.5 x 28.5 inches | 30.5 x 13.5 x 25 in |
| 38.75 x 13.5 x 32.5 inches | |||||
(without bypass) |
| 695 x 345 x 725 mm | 775 x 347 x 635 mm |
| 985 x 345 x 825 mm | |||||
(H x W x D) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
UPS Dimensions with |
| 28.6 x 13.5 x 35 inches | 31.9 x 13.5 x 31.5 in |
| 40.1 x 13.5 x 39 inches | |||||
Internal Bypass |
| 730 x 345 x 890 mm | 810 x 347 x 800 mm |
| 1020 x 345 x 990 mm | |||||
(H*** x W x D) |
|
|
|
|
|
|
|
|
|
|
| FBT21, FBT22: 27.25 x 13.5 x 28.5 in. (695 x 345 x 725 mm); add 2.6 in/66 mm to depth for connection box. | |||||||||
Battery Cabinet | ||||||||||
Dimensions (H x W x D) | FBT31, FBT32: 38.75 x 13.5 x 32.5 in. (985 x 345 x 825 mm); add 2.6 in./66 mm to depth for connection box. | |||||||||
|
|
|
|
|
|
|
|
|
|
|
*Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown are for the U.S. and Canada.
**At 0.7 leading or distortion power factor. Size output protection according to all applicable local or national codes.
***Height includes switch.
22