900 Specifications

Model

0800-2000

0800-3000

0800-4500

0800-6000

0800-7500

 

2 kVA/1.4 kW

3 kVA/2.1 kW

4.5 kVA/3.2 kW

6 kVA/4.2 kW

7.5 kVA/5.3 kW

 

 

 

 

 

 

 

 

AC Input Voltage

110 = 22 amps

110 = 30 amps

110 = 40 amps

208

= 28 amps

208

= 36 amps

and Current

115 = 22 amps

115 = 30 amps

115 = 40 amps

220

= 28 amps

220

= 36 amps

 

120

= 22 amps

120

= 30 amps

120

= 40 amps

230

= 28 amps

230

= 36 amps

 

127

= 22 amps

127

= 30 amps

127

= 40 amps

240

= 28 amps

240

= 36 amps

 

208

= 12 amps

208

= 16 amps

208

= 20 amps

 

 

 

 

 

220

= 12 amps

220

= 16 amps

220

= 20 amps

 

 

 

 

 

230

= 12 amps

230

= 16 amps

230

= 20 amps

 

 

 

 

 

240

= 12 amps

240

= 16 amps

240

= 20 amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recommended Input

120

= 30-amp

120

= 40-amp

120

= 50-amp

208

= 35-amp

208

= 45-amp

Service for 60 Hz U.S.

208

= 15-amp

208

= 20-amp

208

= 25-amp

240

= 35-amp

240

= 45-amp

Models*

240

= 15-amp

240

= 20-amp

240

= 25-amp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Voltage and

120

= 16 amps

120

= 25 amps

120

= 37 amps

120

= 50 amps

120

= 62 amps

Maximum Output

127

= 15 amps

127

= 23 amps

127

= 35 amps

127

= 47 amps

127

= 59 amps

Current in Amps**

208

= 9 amps

208

= 14 amps

208

= 21 amps

208

= 28 amps

208

= 36 amps

 

220

= 9 amps

220

= 13 amps

220

= 20 amps

220

= 27 amps

220

= 34 amps

 

230

= 8 amps

230

= 13 amps

230

=19 amps

230

= 26 amps

230

= 32 amps

 

240

= 8 amps

240

= 12 amps

240

= 18 amps

240

= 25 amps

240

= 31 amps

 

 

 

 

 

 

Efficiency on AC Line

90%

90%

90%

89%

89%

 

 

 

 

 

 

 

On Line BTU/hour:

703

 

1024

1427

1707

2116

kW/hour:

0.206

0.300

0.418

0.500

0.620

 

 

 

 

 

 

Audible Noise (dB)

<45 dB

<45 dB

<45 dB

<45 dB

<45 dB

 

 

 

 

 

 

 

 

 

 

 

Typical Standard

 

 

 

 

 

 

 

 

 

 

Runtime (minutes)

 

 

 

 

 

 

 

 

 

 

Full Load:

11 minutes

17 minutes

10 minutes

16 minutes

12 minutes

Half Load:

23 minutes

36 minutes

22 minutes

38 minutes

27 minutes

 

 

 

 

 

 

 

 

 

 

 

Weights:

 

 

 

 

 

 

 

 

 

 

No Internal Bypass,

 

 

 

 

 

 

 

 

 

 

Standard Batteries:

280 lbs. (127 kg)

327 lbs. (148.3 kg)

383 lbs. (173.7 kg)

563 lbs. (255.4 kg)

635 lbs. (288 kg)

Internal Bypass,

 

 

 

 

 

 

 

 

 

 

Standard Batteries:

303 lbs. (137.4 kg)

350 lbs. (158.8 kg)

410 lbs. (186 kg)

590 lbs. (267.6 kg)

662 lbs. (300.3 kg)

Battery Cabinet,

 

 

 

 

 

 

 

 

 

 

Standard Batteries:

 

 

 

 

 

 

 

 

 

 

FBT21

235 lbs. (106.6 kg)

235 lbs. (106.6 kg)

235 lbs. (106.6 kg)

235 lbs. (106.6 kg)

235 lbs. (106.6 kg)

FBT22

355 lbs. (161 kg)

355 lbs. (161 kg)

355 lbs. (161 kg)

355 lbs. (161 kg)

355 lbs. (161 kg)

FBT31

418 lbs. (189.6 kg)

418 lbs. (189.6 kg)

418 lbs. (189.6 kg)

418 lbs. (189.6 kg)

418 lbs. (189.6 kg)

FBT32

660 lbs. (299.4 kg)

660 lbs. (299.4 kg)

660 lbs. (299.4 kg)

660 lbs. (299.4 kg)

660 lbs. (299.4 kg)

 

 

 

 

 

 

 

 

UPS Dimensions

 

27.25 x 13.5 x 28.5 inches

30.5 x 13.5 x 25 in

 

38.75 x 13.5 x 32.5 inches

(without bypass)

 

695 x 345 x 725 mm

775 x 347 x 635 mm

 

985 x 345 x 825 mm

(H x W x D)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS Dimensions with

 

28.6 x 13.5 x 35 inches

31.9 x 13.5 x 31.5 in

 

40.1 x 13.5 x 39 inches

Internal Bypass

 

730 x 345 x 890 mm

810 x 347 x 800 mm

 

1020 x 345 x 990 mm

(H*** x W x D)

 

 

 

 

 

 

 

 

 

 

 

FBT21, FBT22: 27.25 x 13.5 x 28.5 in. (695 x 345 x 725 mm); add 2.6 in/66 mm to depth for connection box.

Battery Cabinet

Dimensions (H x W x D)

FBT31, FBT32: 38.75 x 13.5 x 32.5 in. (985 x 345 x 825 mm); add 2.6 in./66 mm to depth for connection box.

 

 

 

 

 

 

 

 

 

 

 

*Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown are for the U.S. and Canada.

**At 0.7 leading or distortion power factor. Size output protection according to all applicable local or national codes.

***Height includes switch.

22