Item and Sample | Password to | Range | Explanation |
Display | Change |
|
|
|
|
|
|
3 10 | No change | Not | Percent of Full Load. The percentage of the FERRUPS’ total |
% Full Load | allowed. | applicable. | capacity that your equipment is using. |
pctfload 90 % |
|
|
|
|
|
|
|
3 11 | No change | Not | The power factor of your equipment; the difference in the way it |
Power Factor | allowed. | applicable. | draws voltage and current. Power factor equals Watts Out (parameter |
powerfact 0.70 |
|
| 3 8) divided by VA Out (parameter 3 7). |
|
|
|
|
3 12 | No change | Not | During normal operation, this is the frequency of power the |
Output Frequency | allowed. | applicable. | FERRUPS is receiving from the AC input source. If this value falls |
freqout 60.4 Hz |
|
| outside preset limits, the FERRUPS goes to battery power. When the |
|
|
| FERRUPS is running on battery power, this is the frequency the |
|
|
| FERRUPS is supplying to your equipment. |
|
|
|
|
3 13 | No change | The FERRUPS battery voltage. the FERRUPS will alarm if this | |
Battery Volts | allowed. |
| value is too low or too high. |
vbatt 48.51 V |
|
|
|
|
|
|
|
3 14 | No change | Not | The estimated runtime remaining, that is, the amount of time the |
Run Time | allowed. | applicable. | FERRUPS will continue to support your equipment when the |
runtime 12 m |
|
| FERRUPS switches to battery power. The FERRUPS will alarm if |
|
|
| this value falls below a preset limit. |
|
|
|
|
3 15 | No change | The temperature (in Celsius) inside the FERRUPS. The FERRUPS | |
Unit Ambient Temp | allowed. |
| will alarm and shut down if this value is too high. |
ambtemp 23.0 c |
|
|
|
|
|
|
|
3 16 | No change | Not | A code used to identify the EEPROM configuration of parameters |
EEPROM Stat Word | allowed. | applicable. | and logs. |
eeword 0000 hex |
|
|
|
|
|
|
|
| Item and Sample | Password to | Range | Explanation |
| Display | Change |
|
|
|
|
|
|
|
4 | 1 | No change | The FERRUPS model number. | |
Model Number | allowed. |
|
| |
mdlnum |
|
|
| |
|
|
|
|
|
4 | 2 | No change | Your FERRUPS unit’s serial number. | |
Serial Number | allowed. |
|
| |
serialno 12345678 |
|
|
| |
|
|
|
|
|
4 | 3 | No change | This value is used by CheckUPS software. | |
Unit ID | allowed. |
|
| |
unitid 0002 |
|
|
| |
|
|
|
|
|
4 | 4 | No change | The version of unit software that your FERRUPS is using. | |
Software Version | allowed. |
|
| |
sftwver 1.15 |
|
|
| |
|
|
|
|
|
4 | 5 | Service | The AC input voltage at which the FERRUPS will switch to battery | |
Brown Out Level |
|
| power. | |
brownlvl 79.8 V |
|
|
| |
|
|
|
|
|
4 | 6 | User | The AC input voltage at which the FERRUPS will switch to battery | |
Batt Amp Hours |
|
| power. | |
batamphr 31.0 hrs |
|
|
| |
|
|
|
|
|
15