Menu 3: System Status Info (continued)

Item and Sample

Password to

Range

Explanation

Display

Change

 

 

 

 

 

 

3 10

No change

Not

Percent of Full Load. The percentage of the FERRUPS’ total

% Full Load

allowed.

applicable.

capacity that your equipment is using.

pctfload 90 %

 

 

 

 

 

 

 

3 11

No change

Not

The power factor of your equipment; the difference in the way it

Power Factor

allowed.

applicable.

draws voltage and current. Power factor equals Watts Out (parameter

powerfact 0.70

 

 

3 8) divided by VA Out (parameter 3 7).

 

 

 

 

3 12

No change

Not

During normal operation, this is the frequency of power the

Output Frequency

allowed.

applicable.

FERRUPS is receiving from the AC input source. If this value falls

freqout 60.4 Hz

 

 

outside preset limits, the FERRUPS goes to battery power. When the

 

 

 

FERRUPS is running on battery power, this is the frequency the

 

 

 

FERRUPS is supplying to your equipment.

 

 

 

 

3 13

No change

10.00-70.00

The FERRUPS battery voltage. the FERRUPS will alarm if this

Battery Volts

allowed.

 

value is too low or too high.

vbatt 48.51 V

 

 

 

 

 

 

 

3 14

No change

Not

The estimated runtime remaining, that is, the amount of time the

Run Time

allowed.

applicable.

FERRUPS will continue to support your equipment when the

runtime 12 m

 

 

FERRUPS switches to battery power. The FERRUPS will alarm if

 

 

 

this value falls below a preset limit.

 

 

 

 

3 15

No change

0.0-150.0

The temperature (in Celsius) inside the FERRUPS. The FERRUPS

Unit Ambient Temp

allowed.

 

will alarm and shut down if this value is too high.

ambtemp 23.0 c

 

 

 

 

 

 

 

3 16

No change

Not

A code used to identify the EEPROM configuration of parameters

EEPROM Stat Word

allowed.

applicable.

and logs.

eeword 0000 hex

 

 

 

 

 

 

 

Menu 4: System ID

 

Item and Sample

Password to

Range

Explanation

 

Display

Change

 

 

 

 

 

 

 

4

1

No change

5-9999

The FERRUPS model number.

Model Number

allowed.

 

 

mdlnum

 

 

 

 

 

 

 

 

4

2

No change

0-99999999

Your FERRUPS unit’s serial number.

Serial Number

allowed.

 

 

serialno 12345678

 

 

 

 

 

 

 

 

4

3

No change

0-9999

This value is used by CheckUPS software.

Unit ID

allowed.

 

 

unitid 0002

 

 

 

 

 

 

 

 

4

4

No change

0-9999

The version of unit software that your FERRUPS is using.

Software Version

allowed.

 

 

sftwver 1.15

 

 

 

 

 

 

 

 

4

5

Service

74.4-192.0

The AC input voltage at which the FERRUPS will switch to battery

Brown Out Level

 

 

power.

brownlvl 79.8 V

 

 

 

 

 

 

 

 

4

6

User

10.0-1000.0

The AC input voltage at which the FERRUPS will switch to battery

Batt Amp Hours

 

 

power.

batamphr 31.0 hrs

 

 

 

 

 

 

 

 

15