Alarm Message

 

Morse

What It Means

How to React

 

 

Code

 

 

 

 

 

 

 

 

K Circuit Breaker

 

• —

Your equipment is drawing more current

The least important equipment should be

Warning

 

(K)

(amps) than the UPS is designed to provide.

disconnected from the UPS. To determine how

Shutdown

 

 

 

(See your model’s output current rating.) The

much equipment needs to be disconnected, you

 

 

 

 

unit will shut down; the time until shutdown

can shut off the equipment one device at a time

 

 

 

 

depends on the amount of overcurrent.

until the alarm stops.

 

 

 

 

 

 

M Check Battery

 

The batteries have failed the automatic test.

If the UPS has separate battery cabinets, make

vbatt 50.00 V

 

(M)

 

sure the DC switch is on at each cabinet. If it is,

batamphr 85.0 hrs

 

 

 

 

or if the UPS has no separate battery cabinets,

runtimek 0.55

 

 

 

 

phone Best Power’s Worldwide Service or the

 

 

 

 

 

nearest Best Power office.

 

 

 

 

 

 

N Check Inverter

 

The UPS has detected a problem in the

Phone Best Power’s Worldwide Service or the

vbatt 50.00 V

 

(N)

inverter, which is the circuitry that allows the

nearest Best Power office.

 

 

 

 

UPS to run on battery power. The UPS will

 

 

 

 

 

not be able to run on battery power.

 

 

 

 

 

 

 

O Memory Check

The UPS has failed the automatic memory

Shut down your equipment or bypass the UPS,

mdlnum 5

 

(O)

test. This problem could be caused by a

and turn the UPS off. Phone Best Power’s

 

 

 

 

microprocessor problem.

Worldwide Service or the nearest Best Power

 

 

 

 

 

office.

 

 

 

 

 

P Emergency

• —

— •

The Emergency Power Off feature has been

To restart the UPS, press the On/Off button on

Power Off

 

(P)

activated. (See Section 703 and the

the back of the FERRUPS. Then, press any

EPO Mode = 2

 

 

 

Installation Manual.)

button at the front panel.

 

 

 

 

 

 

Q Check MOV’s

• —

The UPS has detected a problem with an

Phone Best Power’s Worldwide Service or the

 

 

(Q)

MOV (Metal Oxide Varistor) inside the unit.

nearest Best Power office.

 

 

 

 

 

 

R Check Fan

 

• —

The UPS has detected a problem with the

Phone Best Power’s Worldwide Service or the

 

 

(R)

rotation of its internal fan.

nearest Best Power office.

 

 

 

 

 

 

700 Communication

701 Communication Options

Best Power offers several methods of communicating with your FERRUPS:

CheckUPS Software: Each FERRUPS unit ships with CheckUPS power monitoring and unattended shutdown software. To begin installing CheckUPS, see the instructions in the CheckUPS CD case.

CheckUPS uses an RS-232 serial link to communicate with the FERRUPS, and it provides you with up-to-date graphics of UPS power and system data and power flow. CheckUPS also gives you a complete record of critical power events, and it notifies you of important UPS or power information. If there is a power outage and the FERRUPS battery power becomes low, CheckUPS can automatically shut down your computer system before the UPS Low Battery shutdown to protect your data.

RS232

Communication: You can connect a terminal or a computer with terminal emulation software to the FERRUPS’ communication port. This allows you to receive information from the FERRUPS or send commands in order to display and program parameters. For more information, call the nearest Best Power office.

19