2.Find the alarm in the table below, and follow the instructions in the third column of the table. To clear an alarm when the problem has been solved, press the middle button below the display. If the problem that caused the alarm is still present, the alarm will sound again after a short delay.
Alarm Message | Morse | What It Means | How to React | ||
| Code |
|
| ||
|
|
|
|
|
|
A Low Battery |
| • — |
| The UPS has shut down because the battery | Before this alarm sounded, you should have |
vbatt 40.0 V |
| (A) |
| voltage is too low for the UPS to continue | received a Low Runtime alarm (D) to warn you |
lowbatv 41.0 V |
|
|
| operating on battery power. The battery | to shut down your equipment. Shortly after |
minbattv 38.34 |
|
|
| charge is low because the UPS was running | acceptable AC input power returns, the UPS will |
|
|
|
| on battery power or because the DC switch | automatically restart and begin recharging the |
|
|
|
| on one or more separate battery cabinets was | batteries. Once the UPS restarts, you can restart |
|
|
|
| off. | your equipment and resume normal operation. |
|
|
|
|
|
|
C High Battery | — | • — | • | The battery voltage is too high. There may | |
vbatt 60.01 V |
| (C) |
| be a problem with the parameter settings, | |
hibatv 59.6 V |
|
|
| batteries, or charging circuit. |
|
maxbattv 60.01 V |
|
|
|
|
|
|
|
|
|
|
|
D Low Runtime | — | • • |
| The unit is running on battery power, but the | Shut down your equipment and the UPS to |
runtime 0 m |
| (D) |
| amount of time that it can continue to do this | conserve battery power. When AC input power |
lowruntm 3 m |
|
|
| is low. | returns, turn the FERRUPS on again. If you |
|
|
|
|
| leave the FERRUPS on after this alarm sounds, |
|
|
|
|
| it will soon sound alarm A and shut down, and it |
|
|
|
|
| will automatically restart when AC input power |
|
|
|
|
| returns. |
|
|
|
|
|
|
E Low AC Out |
| • |
| The UPS has shut down because AC output | Shut down your equipment or bypass the UPS, |
acvout 220 V |
| (E) |
| voltage is low. | |
lowvoshdn 0 V |
|
|
|
| |
maxva 0.00 KVA |
|
|
|
| |
|
|
|
|
| |
F High AC Out | • • — | • | The UPS has shut down because AC output | ||
acvout 250 V |
| (F) |
| voltage is high. | |
maxacvo 251 V |
|
|
|
|
|
|
|
|
|
|
|
G Output Overload | — | — | • | Your equipment is drawing more power | The least important equipment should be |
pctfload 105 % |
| (G) |
| (watts) than the UPS is designed to provide. | disconnected from the UPS. To determine how |
|
|
|
| (See your model’s watt rating.) The unit will | much equipment needs to be disconnected, you |
|
|
|
| shut down after 2 minutes. | can shut off the equipment one device at a time |
|
|
|
|
| until the alarm stops. |
|
|
|
|
| |
H High Ambient | • • • • |
| The temperature inside the unit is too high. If | ||
Temp |
| (H) |
| the temperature continues to rise, the UPS | |
ambtemp 75.0 c |
|
|
| will eventually shut down. | |
atmpalrm 70.0 c |
|
|
|
| temperature, and make sure nothing is blocking |
|
|
|
|
| the UPS vents. If you cannot correct the |
|
|
|
|
| |
|
|
|
|
| |
|
|
|
|
|
|
I Check Power |
| • • |
| There is a problem with the housekeeping | |
Supply |
| (I) |
| supply inside the UPS. If the green light on | |
|
|
|
| the UPS front panel is blinking, the UPS has |
|
|
|
|
| switched to Line Condition mode, which |
|
|
|
|
| means it cannot operate on battery power. If |
|
|
|
|
| this happens, the UPS will not be able to |
|
|
|
|
| supply output power during a power outage. |
|
|
|
|
|
|
|
J User Test Alarm | • — | — | — | You can start a User Test alarm by displaying | To stop the User Test alarm, press any button on |
|
| (J) |
| parameter (number 2 13) and pressing ¿. | the front panel. |
|
|
|
|
|
|
18