HEAT PUMP TERMINAL OUTPUTS

Refer to equipment manufacturers’ instructions for specific system wiring information.

You can configure the thermostat for use with the following heat pump system types:

HEAT PUMP TYPE 1. Single- stage compressor system; gas or electric backup.

HEAT PUMP TYPE 2. Multi-stage or two-compressor system; gas or electric backup.

HEAT PUMP TYPE 3. System requiring separate signals for heat (W1, W2) and cool (Y1); gas or electric backup.

This thermostat is designed to operate a single-transformer system. If you have a two-transformer system, cut and tape off one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining trans- former with a 75VA Class II transformer. After disconnecting one transformer, the two commons must be jumpered together.

Use the terminal output information on the next page to help you wire the thermostat properly for your heat pump system type. After wiring, see CONFIGURATION section for proper thermostat configuration.

9

Installation

Page 11
Image 11
Emerson 1F92 manual Heat Pump Terminal Outputs