| Operator Control and Display Panel |
Table 19 Descriptions of UPS menus and data window items (continued) | ||
|
|
|
Menu Type | Item Type | Explanation |
|
|
|
| Battery maintenance test | This test performs a partial discharge of the battery to obtain a rough estimate |
|
| of the battery capacity. Load must be between 20% and 80%. |
| Battery capacity test | This test performs a full discharge of the battery to obtain a precise measure of |
|
| the battery capacity. Load must be between 20% and 80%. |
Command | System test | This is a |
| window appears about 5 seconds later to show the results. | |
(start/stop |
| |
battery & | Stop testing | Manually stops a battery maintenance test, battery capacity test or system |
system |
| test. |
tests) |
|
|
Freshening Charge | Allows a temporary Equalize charge for the batteries. This charge is | |
|
| configurable for 1 to 36 hours. |
| Stop Freshening Charge | Manually stops a Freshening Charge |
|
|
|
| Modem | Manually enable the modem’s |
| enable |
|
| UPS version | Provides UPS firmware version numbers for the inverter, rectifier and software |
Version |
| display board. |
| UPS model | Provides UPS model |
8.9Language Selection
The LCD menus and data display are available in 12 languages (Chinese, Dutch, English, French, German, Italian, Japanese, Polish, Portuguese, Russian, Spanish and Swedish). To select a different language:
•From the main menu, press the F1 (Shift) key to move the cursor to the menu at the top of the screen.
•Press F2 and F3 (left and right arrows) as needed to select the Language menu.
•Press F1 (shift) to move the cursor to the data and settings area of the LCD.
•Use F2 and F3 (up and down) to select the required language.
•Press the F4 (enter) key to accept the language selection.
•Return to the main menu by repeatedly pressing F1 (ESC) as needed; all text on the LCD will now be displayed in the selected language.
Figure 46 Language selection
Liebert NX | 12:30:36 | |
Single | Normal |
Battery | History | Language | ||
|
| English |
| DEUTSCH |
POLSKI |
| FRANCAIS |
| ITALIANO |
ESPAÑOL |
| NEDERLANDS |
| SVENSKA |
|
| РУССКИЙ | PORTUGUêS | |
Input disconnect closed | 12:30 | |||
Output disconnect closed | 12:30 | |||
Bypass disconnect open | 12:30 | |||
|
|
|
| ? |
F1 | F2 | F3 | F4 | HELP |
|
| 64 |
|
|