Emerson 480V Distance to connection points on the Liebert NX UPS, Parallel system current table

Models: 480V

1 108
Download 108 pages 52.85 Kb
Page 97
Image 97

Specifications and Technical Data

Liebert NX, then add the appropriate length from the table and adequate slack for repair and mainte- nance.

Table 26 Distance to connection points on the Liebert NX UPS

 

Distance

 

 

 

 

From Floor

From Top of Unit

Connection Point on UPS

in. (mm)

in. (mm)

Bypass AC input supply

13 (330)

66 (1676)

 

 

 

UPS output AC

13 (330)

66 (1676)

 

 

 

Battery power

13 (330)

66 (1676)

 

 

 

Auxiliary cables: Monitor board (U2)

67 (1702)

11 (279)

 

 

 

Liebert IntelliSlot Communications

60 (1524)

19 (483)

 

 

 

Ground

13 (330)

66 (1676)

 

 

 

Parallel Board

70 (1780)

11 (279)

 

 

 

Table 27 Parallel system current table

 

 

 

System I/P

 

System

 

Nominal

Output

System

 

 

Voltage

System Max

Input OCPCB

O/P Voltage

O/PCurrent

OCPCB

Size

Type

kVA

(VAC)

Input Current

Size (A)

(VAC)

Rating (A)

Size (A)

 

E

80

480V

202.5

300

480V

144.3

200

 

120

480V

135.0

200

480V

96.2

125

 

 

1+1

E1

80

480V

202.5

300

480V

144.3

200

120

480V

135.0

200

480V

96.2

125

 

 

 

E2

80

N/A

N/A

N/A

480V

144.3

200

 

120

N/A

N/A

N/A

480V

96.2

125

 

 

 

E

80

480V

405.0

600

480V

288.7

400

 

120

480V

270.0

350

480V

192.5

250

 

 

2+1

E1

80

480V

405.0

600

480V

288.7

400

120

480V

270.0

350

480V

192.5

250

 

 

 

E2

80

N/A

N/A

N/A

480V

288.7

400

 

120

N/A

N/A

N/A

480V

192.5

250

 

 

 

E

80

480V

607.5

800

480V

433.0

600

 

120

480V

405.0

600

480V

288.7

400

 

 

3+1

E1

80

480V

607.5

800

480V

433.0

600

120

480V

405.0

600

480V

288.7

400

 

 

 

E2

80

N/A

N/A

N/A

480V

433.0

600

 

120

N/A

N/A

N/A

480V

288.7

400

 

 

Use wiring rated at 75°C or greater.