Emerson 480V Bypass voltage is beyond the normal range, Bypass voltage exceeds the limit

Models: 480V

1 108
Download 108 pages 52.85 Kb
Page 102
Image 102

UPS Status Messages

Table 36

UPS status messages

 

 

Event Message

Description / Suggested Action (if any)

 

 

 

 

 

This alarm is triggered by an inverter software routine when the amplitude or frequency of

 

 

bypass voltage is beyond the normal range.

 

 

The amplitude threshold is fixed for positive and negative 10% rating.

 

 

This alarm automatically resets once the bypass voltage goes normal.

Bypass Unable to Trace

First verify that the bypass voltage and frequency displayed on the panel is within the selected

range. Note here the rated voltage and frequency are specified by “Output voltage level” and

 

 

 

 

“Output frequency level” respectively.

 

 

If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency

 

 

presented to the UPS. Check the external supply if it is found to be faulty.

 

 

Contact Liebert Global Services at 800-543-2378 for assistance.

 

 

This alarm is triggered by an inverter software routine when the amplitude or frequency of

 

 

bypass voltage exceeds the limit.

 

 

This alarm automatically resets once the bypass voltage goes normal.

 

 

First check whether there are relevant alarms such as “Bypass disconnect open,” “Bypass

 

 

phase reverse” and “Mains neutral lost.” If they appear, solve them first.

 

 

Then verify that the bypass voltage and frequency displayed on the panel is within the bypass

Bypass Abnormal

limit. Note here the rated voltage and frequency are specified by “Output voltage level” and

 

 

“Output frequency level” respectively.

 

 

If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency

 

 

presented to the UPS. Check the external bypass supply if it is found to be faulty. If the utility is

 

 

likely to trigger this alarm frequently, the bypass limit can be increased through the configuration

 

 

software according to the customer’s agreement.

 

 

Contact Liebert Global Services at 800-543-2378 for assistance.

 

 

This alarm is triggered by an inverter software routine when the inverter and bypass waveforms

 

 

are misaligned by more than 6 degrees in phase. This alarm resets automatically once the

 

 

condition clears.

Inverter Asynchronous

First check if the alarm “Bypass unable to trace” or “Bypass abnormal” occurs. If so, solve it first.

Verify the waveform of the bypass voltage.

 

 

 

 

Contact Liebert Global Services at 800-543-2378 for assistance.

 

 

 

Inverter Fault

This alarm indicates a fault condition exists within the inverter.

Contact Liebert Global Services at 800-543-2378 for assistance.

 

 

Output Voltage Abnormal

This alarm indicates the inverter voltage waveform is abnormal.

Contact Liebert Global Services at 800-543-2378 for assistance.

 

 

Input Current Abnormal

This alarm indicates the rectifier input current is abnormal.

Contact Liebert Global Services at 800-543-2378 for assistance.

 

 

 

 

The temperature of the inverter filter inductor or inverter common mode inductor is too high to

 

 

keep inverter running.

 

 

This alarm is triggered by the signal from a thermostat mounted in the inverter filter inductor.

 

 

The UPS would recover automatically after a 5 minute delay from the disappearance of the

 

 

overtemperature signal.

Inv. Inductor Overtemp.

If the overtemperature condition is true then check for and verify:

 

 

High ambient air temperature.

 

 

Blocked cooling airway

 

 

Any fan failure

 

 

Prolonged inverter overload.

 

 

Contact Liebert Global Services at 800-543-2378 for assistance.

 

 

The temperature of the inverter heat sink is too high to keep inverter running.

 

 

This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter

 

 

bridge heat sink.

 

 

The UPS will recover automatically after a 5 minute delay from the disappearance of the

 

 

overtemperature signal.

Inverter Overtemp.

If the overtemperature condition is true then check for and verify:

 

 

high ambient air temperature.

 

 

blocked cooling airway.

 

 

any fan failure.

 

 

prolonged inverter overload.

 

 

Contact Liebert Global Services at 800-543-2378 for assistance.

Fan Fault

 

At least one of the cooling fans has failed. Contact Liebert Global Services at 800-543-2378 for

 

assistance.

 

 

94

Page 102
Image 102
Emerson 480V user manual Bypass voltage is beyond the normal range, Bypass voltage exceeds the limit, Condition clears

480V specifications

The Emerson 480V power systems play a critical role in modern industrial applications, providing reliable and efficient power distribution. These systems are designed for facilities that require robust performance and operational efficiency while adhering to safety regulations. With voltage ratings at 480V, they cater primarily to industries such as manufacturing, data centers, and commercial buildings.

One of the main features of the Emerson 480V systems is their scalability. These systems can be easily adapted and expanded as operational demands grow, thereby reducing initial investment costs and providing a flexible solution for evolving business needs. This ability to scale is crucial in a fast-paced environment where demands can change rapidly.

The Emerson 480V systems also incorporate advanced technologies for improved performance and safety. One key technology is the use of smart grid solutions. This enables real-time monitoring, diagnostics, and control, allowing facility managers to optimize energy consumption and reduce operational costs. Furthermore, these systems often include integrated protection devices that enhance safety measures by minimizing the risk of electrical faults, overloads, or short circuits.

Energy efficiency is another characteristic that distinguishes Emerson 480V systems from traditional alternatives. With advanced power management features, these systems effectively reduce energy waste and lower electricity bills. Emerson’s commitment to sustainability is evident in its designs, which aim to minimize environmental impact through energy-efficient technologies.

The build quality of Emerson 480V systems is also noteworthy. They are designed to withstand harsh industrial environments and are constructed with high-grade materials that promote longevity and reliability. The modular design allows for easy maintenance and repair, which further extends the lifespan of the system.

Additionally, Emerson 480V systems are equipped with user-friendly interfaces that facilitate ease of operation. This ensures that operators can efficiently manage and control power distribution without extensive training. The combination of performance, scalability, safety features, and user-centric design makes Emerson 480V systems an ideal choice for businesses looking to enhance their electrical infrastructure.

In summary, Emerson 480V power systems are a leading solution for industrial power distribution, characterized by their scalability, smart technology integration, energy efficiency, robust build quality, and user-friendly operation. These attributes make them a valuable investment for any organization aiming to improve its electrical management and operational performance.