Emerson 480V user manual 250 10 N*m

Models: 480V

1 108
Download 108 pages 52.85 Kb
Page 99
Image 99

Specifications and Technical Data

Table 32 Cable size tightening torque at Liebert NX 80kVA UPS terminals

 

Cable Size

Torque to Tighten

Bus Type

(Copper Wire Only)

Terminal Bus & Lug Body

 

 

 

Main Input

2/0

10 N*m

(Single Input)

 

 

Main Input

2/0

10 N*m

(Dual Input)

 

 

Bypass Input

1/0

10 N*m

(Dual Input)

 

 

Output

1/0

10 N*m

 

 

 

Table 33 Cable size tightening torque at Liebert NX 100kVA UPS terminals

 

Cable Size

Torque to Tighten

Bus Type

(Copper Wire Only)

Terminal Bus & Lug Body

 

 

 

Main Input

4/0

10 N*m

(Single Input)

 

 

Main Input

4/0

10 N*m

(Dual Input)

 

 

Bypass Input

2/0

10 N*m

(Dual Input)

 

 

Output

2/0

10 N*m

 

 

 

Table 34 Cable size tightening torque at Liebert NX 120kVA UPS terminals

 

Cable Size

Torque to Tighten

Bus Type

(Copper Wire Only)

Terminal Bus & Lug Body

 

 

 

Main Input

250

10 N*m

(Single Input)

 

 

Main Input

250

10 N*m

(Dual Input)

 

 

Bypass Input

4/0

10 N*m

(Dual Input)

 

 

Output

4/0

10 N*m

 

 

 

91

Page 99
Image 99
Emerson 480V user manual 250 10 N*m