4-4 Setup Program – Serial Connection
Alarms - Email Address
Alarms - ATS Power Manager Setting
Alarms - Engine PM Details
Thin Web Server
6.Click the Email Address lower tab. Then enter the
Note: Make sure outgoing mailserver is configured properly and working. This functionality can be tested with third party
7.Click the ATS Power Manager Setting lower tab. The Network 1 Power Managers (addresses) are displayed first. For each Power Manager (PM) address click the
-is with an ATS, select icon 1.
-is with a circuit breaker, select icon 3 or 4.
-is not associated with an ATS or a CB, select icon 2. Then click View Network 2 Settings and select icons for those PMs.
8.Click the Engine PM Details lower tab. Network 1 & 2 Engine Power Manager (addresses
9.Click the Engine Power Manager Setting lower tab. Select the check boxes Status Inputs and/or Discrete Outputs that you want included in alarms monitoring.