System Interface Circuit Card
The system interface circuit card contains test points to externally monitor bay voltage
and bay load. Refer to Figure 2-2.
Figure 2-2
System Interface Circuit Card
TP3 (+) and TP4 (-)
Bay Load
Shunt Monitoring
TP1 (+) and TP2 (-)
Bay Voltage
Monitoring
J7
TB2
J1 1
1
1
1
J2
J3
J4
J8
TB1
TP1 TP2 TP3 TP4
J5
J10
Bay Load Shunt Scale
List 21, 1-Row Cabinet
800A/ 25 mV
32Aper mV
List 22, 2-Row Cabinet
2000A/ 2 5mV
80Aper mV
List 23, 3-Row Cabinet
2500A/ 2 5mV
100Aper mV
List 24, 4-Row Cabinet
2500A/ 2 5mV
100Aper mV