User Instructions UM582127000
Spec. No. 582127000 (Model 721NPBB) Issue AC, January 2, 2013
Chapter 4. Troubleshooting and Repair Page 33
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-6 (cont’d on next page)
Replacing a GJ/218 Circuit Breaker (1-Pole)
1/4"Hardened
FlatWasher
1/4"Belleville
LockWasher
1/4-20x 3/4Bolt
(2places)
Torqueto 60 in-lbs.
OFF ON
Applyanti-oxidizing compound to busbar mating
surfacesbefore mounting circuit breakers.
INSTALLINGCIRCUIT BREAKER GUARD
INSTALLINGCIRCUIT BREAKER
Alarmjumper connector.
Holesto route shunt j umperthrough (if applicable).
ALARMWIRING (BREAKERS W/OUT SHUNTS) ALARMWIRING (BREAKERS WITH SHUNTS)