Figure 4-18
Replacing a Battery Disconnect Contactor
in a 1-Row Distribution Cabinet
Battery
Disconnect
Contactor
Applyelectrical anti-oxidizing
compoundto busbar mating surfaces.
Componentsremoved in
illustrationfor clarity only.
Contactorstyles vary
betweenmanufacturers.
Front
5/16-18x 1Bolt
5/16"Belleville Lock Washer
5/16"Belleville Lock Washer
(concaveside of Belleville
LockWashers face each other)
5/16"Hardened Flat Washer
(4places)
Torqueto 100 in-lbs.
White/BlackWire
BrownWire
Brown/WhiteWire
Red/WhiteWire
BrownWire
Brown/WhiteWire White/BlackWire
Red/WhiteWire