Page 34 Chapter 4. Troubleshooting and Repair
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-6 (cont’d from previous page)
Installing a GJ/218 Circuit Breaker (2-Pole, 3-Pole, 4-Pole)
1/4"Hardened
FlatWasher
1/4"Belleville
LockWasher
1/4-20x 3/4Bolt
(4places / 2-pole brk,
6places / 3-pole brk,
8places / 4-pole brk)
Torqueto 60 in-lbs.
Applyanti-oxidizing compound to busbar mating
surfacesbefore mounting circuit breakers.
OFF ON
INSTALLINGCIRCUIT BREAKER GUARD
INSTALLINGCIRCUIT BREAKER Alarmjumper connectors.
Holesto route shunt jumper through (if a pplicable).
ALARMWIRING (BREAKERS W/OUT SHUNTS) ALARMWIRING (BREAKERS WITH SHUNTS)
Busbar
2-polebreaker shown.
3-poleand 4-pole breakerssimilar.