Page 50 Chapter 4. Troubleshooting and Repair
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-15
Optional LVD Driver Lite Circuit Card Connector Locations
Notes:
1. Connects up to (2) LVD
contactors rated at 600A or less.
2. Only one(1) contactor per level
can be accommodated. J2 and J3
are on Level 2, only one (1) of these
connectors can be used at a time.
3. Switch and indicator located
on circuit card installed in
Main Bay only.
J1
ToLVLD contactor, uses ACU+
LVD1control setting (Level 1).
J3
ToLVLD contactor, uses ACU+
LVD2control setting (Level 2).
J2
ToLVBD contactor, uses ACU+
LVD2control setting (Level 2).
Can only beused if it is contained
in a List 21 (1-row) cabinet.
J1J3
J2
S1
DO NOT change a Low Voltage
Load Disconnect contactor to
LVDControl Level 2 (LVD2) if
the system is furnished with a
Low VoltageBattery Disconnect
contactor.