Auxiliary 120V / 400VA Power

Auxiliary 120V / 400VA Power

The GXT5VBATTW120 battery cabinet also provides a transformer to provide up to 400VA of 120V power.

Dynamic Bypass

The GXT5000R-208 provides an alternate path for utility power to the connected load in the unlikely event of a UPS malfunction, such as overload, overtemperature, or an internal UPS failure. If a malfunction does occur, the UPS automatically transfers the connected load to bypass. Bypass operation is indicated by an alarm and illuminated Bypass LED (other LEDs also may be illuminated to indicate the diagnosed problem). To manually transfer the con- nected load from the inverter to bypass, press the Standby button Dynamic Bypass once.

NOTE

The bypass power path does NOT protect the connected equipment from disturbances on the utility supply, such as spikes, sags, and failure.

6