TROUBLESHOOTING
This section presents various problems a user might encounter. Use this information to deter- mine whether external factors cause the problem and how to remedy the situation.
1.The Fault LED will illuminate, indicating the UPS detected a problem.
2.An alarm will sound, alerting that the UPS requires attention.
3.One or more additional load/battery level LED indicators will be illuminated to provide a diagnostic aid to the operator, as shown below:
Fault | A B C D E |
| |
LED |
|
F |
|
4.Record the LED condition and horn condition. Turn off the 30A AC input circuit breaker on the rear of the UPS and restart the UPS based on the Operating Instructions in this manual.
Table 2 | LED indicators |
| |
LED status | Diagnosis | Audible alarm | |
|
|
| |
All LEDs on | AC input overvoltage | Continuous beep | |
|
|
|
|
|
| On bypass due to overtemperature condition until the UPS | Continuous beep |
A, F on |
| cools, then |
|
|
| Or off due to very high temperatures. | — |
|
|
|
|
D, F on |
| Battery overvoltage | Continuous beep |
|
|
|
|
E, F on |
| Battery mode overload | |
|
|
| every 1 second |
A, D, F on |
| Inverter output short | Continuous beep |
Line LED |
| Input AC present, but exceeds PFC input requirements | — |
flashing |
| (> 276 or < 170) |
|
All battery |
| Battery failure warning | Continuous beep |
capacity LEDs |
|
| |
flashing |
|
|
|
B, C, F on |
| EPO shutdown | Continuous beep |
Other |
| Record condition of LEDs and horn. Contact Liebert technical | — |
|
| support. |
|
If a problem persists, consult your local dealer, Liebert representative or the Liebert World- wide Support