Procedure to confirm the battery count

1.Apply AC input power to the UPS.

2.Turn the UPS output off using the Standby button. If the UPS is in inverter mode, the load must first be transferred to bypass and then to off.

3.Once the UPS output is off, press and hold the Standby button continuously. The Standby button must be held continuously for the duration of this procedure. The UPS will do nothing for the first 10 seconds. After approximately 10 seconds, the LED display will scroll and the horn will beep. When the LED display comes to rest (about 15 seconds after first pressing the Standby button), the battery cabinet count will be displayed on the Load LEDs. The count will display as long as the Standby button is continuously held.

4.If the Standby button is released at any time, the entire procedure must be restarted.

5.Once the battery count is displayed, or at any time if you wish to abort the procedure, you may release the Standby button and restart the UPS using the ON button.

Procedure to change the battery count

This procedure required the simultaneous use of the Standby button and ON button. No other UPS procedure calls for simultaneously pressing the Standby and ON buttons.

The first three steps of this procedure repeats Steps 1 through 3 in the Procedure to con- firm the battery count. However, once the battery count is displayed, you have the option of changing the count. As before, the Standby button must be held continuously for the entire procedure. Releasing the button prematurely will require that the whole process be repeated.

1.Apply AC input power to the UPS.

2.Turn the UPS output off using the Standby button. If the UPS is in inverter mode, the load must first be transferred to bypass and then to off.

3.Once the UPS output is off, press and hold the Standby button continuously. After approximately 10 seconds, the LED display will scroll and the horn will beep. When the LED display comes to rest (about 15 seconds after first pressing the Standby button), the battery cabinet count will be displayed on the Load LEDs. The count will display as long as the Standby button is continuously held.

4.If the displayed battery count is incorrect, press the ON button for 1 second while simultaneously continuing to hold the Standby button. The display will scroll and the horn will beep, and the battery count will be increased by one.

5.If the desired battery count has not been reached, repeat Step 4. The count can only be increased. After a count of 5 is reached, the count will restart at 1.

6.Once the desired battery count is displayed—or at any time you wish to abort the procedure—you may release the Standby button and restart the UPS using the ON button.

16

Page 20
Image 20
Emerson GXT5000R-208 user manual Procedure to confirm the battery count, Procedure to change the battery count

GXT5000R-208 specifications

The Emerson GXT5000R-208 is a high-performance uninterruptible power supply (UPS) designed to deliver reliable power protection for critical systems in data centers, industrial applications, and other mission-critical environments. This UPS is engineered for efficiency, redundancy, and performance, making it a trusted choice among IT professionals and facility managers.

One of the key features of the GXT5000R-208 is its double-conversion online technology. This technology ensures that the output power is consistent and free from fluctuations, providing pure sine wave output. This feature is particularly important for sensitive electronic equipment, as it maintains the integrity and operational stability of critical systems even in the event of input power disturbances such as surges, sags, or outages.

The GXT5000R-208 is capable of delivering a power capacity of 5000 VA / 5000 W with a nominal input voltage of 208-volt systems. Its advanced design allows for easy adaptability to various configurations, making it suitable for both single-phase and three-phase applications. The UPS is equipped with a wide input voltage range, which enhances its compatibility with different electrical infrastructures.

Another notable characteristic of the Emerson GXT5000R-208 is its modular design. The UPS can be easily expanded or reconfigured according to the changing needs of the facility, offering scalability for future growth. With hot-swappable batteries, users can perform maintenance or upgrades without downtime, ensuring continuous operation.

The GXT5000R-208 also incorporates powerful monitoring and management features. It comes with an intuitive LCD display that provides real-time information regarding the UPS status, battery health, and operational parameters. The UPS can also be integrated with various management software solutions, allowing for remote monitoring and control via SNMP, USB, or RS-232 connections.

Furthermore, the unit is built with a robust battery management system, ensuring optimal battery performance and longevity. Its intelligent charging system reduces the risk of battery overcharging, thus extending battery life and enhancing overall system reliability.

In summary, the Emerson GXT5000R-208 stands out for its reliable double-conversion online technology, scalability, and advanced monitoring capabilities. Its design prioritizes efficiency and adaptability, ensuring that organizations can maintain operational continuity and protect their critical systems against power disruptions. Whether in a data center or industrial setting, the GXT5000R-208 is a dependable UPS solution that meets the demanding requirements of modern power management.