OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS

Turn On

Once the AC supply has been applied to the unit, power will be applied to the load (bypass mode) immediately when the 30 A input circuit breaker is initially closed. Turn the unit ON (inverter mode) by pressing the ON button once.

Manual Bypass

To manually put the unit in Bypass mode, press the Standby button Turn OnManual BypassStandby once. Pressing this button once will cause the load to be transferred to bypass power. Pressing this button a sec- ond time will result in loss of power to the output receptacles and connected loads.

!

Standby

CAUTION

Pressing the Standby/Manual Bypass button during normal operation while the inverter is on will transfer the load to bypass power, if the bypass voltage and frequency are within a safe range.

The bypass power path does NOT protect the connected equipment from disturbances on the utility supply.

To put the unit in Standby mode, press the Standby button

while the unit is in bypass

mode.

 

!CAUTION

Pressing the Standby/Manual Bypass button when the UPS is in bypass mode will shut off power to the output receptacles and connected loads. Turning the unit off leaves the UPS in standby mode. To fully isolate the load from power, open the input circuit breaker.