SECTION 6. Troubleshooting and Maintenance | 6.4 |
6.0 Diagnostics are Via HART | LTM Transmitters |
| |
6.1 Calibration Problems | Gage and Transmitter Installation |
If the transmitter does not appear to calibrate properly, or has an erratic output, check the deadband of the sensor tube and ensure that the float is within the active region of the probe. The active region of the sensor tube is typically marked with 20mA and 4mA stickers when the unit is calibrated before shipment.
If the output is still erratic, try disconnecting the power momentarily by unplugging and
6.2 Magnetic Interface
It is possible for the
If this appears to be the case, a gage float magnet (or any magnet available) may be run along the length of the sensor tube, past the head of the transmitter, in an even motion and without stopping. This will usually clear all such magnetic anomalies.
CAUTION:
Never move a magnet in a perpendicular motion from along the sensor tube. This will always leave a residual field in the waveguide which will cause the transmitter to give an erratic output
6.3 Troubleshooting Power Supply Problems
The
It is found sometimes that additional resistance in the loop is necessary, either in the form of a second load resistor or higher resistance safety barrier. This will appear to limit the maximum output of the transmitter to below 20 mA. The transmitter will generally perform correctly up to this point. To resolve this problem, the voltage of the loop supply must be increased somewhat. Even a slight increase by one volt may be sufficient and many supplies have such an adjustment.
All connections must be checked for improper wiring or polarity before power is applied. The
TERMINAL BOARD
1.Visually inspect
2.Remove bottom flange and install float. Each float is clearly tagged with serial number of the
3.Inspect bottom flange for proper gasket and spring. This spring protects float and keeps it from dropping below the bottom process connection. To determine proper spring length measure “A” dimension of gage. This is the length from the center of the bottom process connection to face of the bottom drain flange. Length of spring should be
(“A” DIMENSION)
EXAMPLE: “A” Dimension is 14”, Float length is 12”, + 2” = 4” Spring Length.
14 – 12 + 2 = 4” spring
4.Float is properly installed if the bottom
NOTE: There is a top spring in the
Transmitter Check-out and Calibration
NOTE: The LTM Series Transmitters are 24VDC Loop powered (2- wire) and require a minimum of 15 Volts at 20 mA.
1.Using a HART compatible loop calibrator, connect the “+” terminal on the LTM to positive lead of calibrator and the
2.With float in the gage at 4mA, the output of the LTM should be 4mA. Connect the HART Communicator to the transmitter. Upon power up, the HART Communicator should read the LRV (lower range value) or 0 inches at 4mA.
3.With float in the gage at 20mA, the output of the LTM should be 20mA. HART should also display URV (upper range value) or span length in inches at 20mA.
4.To insure complete functionality of gage and transmitter, fill the gage chamber with liquid and drain slowly to observe transmitter and gage are tracking properly.
6